Descargar Imprimir esta página

Dräger Pulsar 7000 Serie Instrucciones De Uso página 17

Ocultar thumbs Ver también para Pulsar 7000 Serie:

Publicidad

Idiomas disponibles

Idiomas disponibles

Duct mount gas detectors only:
Loosen the locking nuts (1).
3. Switch on the power supply.
Both transmitter and corresponding receiver of a gas warning system must be set to the same communication channel.
If multiple gas warning systems are installed and the transmitters could interfere with adjacent receivers, a different channel
should be chosen for each gas warning system. Dräger recommends installing the systems in such a way that the flash
direction of one system is opposite to the flash direction of the other system.
Channels 0-11 are available on the receiver.
If transmitter TX S is being used, channels 0 to 7 must be used. If transmitter TX L is being used, channels 8 to 11 must be
used.
1
1
1
en
Operation
05300114_33451
17

Publicidad

loading