- LOW: The Relay open when the measures is lower of setpoint ± hysteresis, and close
when the measure is upper of setpoint ± hysteresis
Priming: It is possible to active the dosing pumps related to the products by hand.
HIGH/LOW examples:
Dosing mode: HIGH
ppm
H ysteresi s
Se t p o i n t
Status
Relay
Op e n
Cl o se
Figure 1 Relay setpoint menu
It is the choice to increase the measurement's value when it falls below a chosen value.
The relay closes if the measurement's value is below the minimum of the range and it opens
when it returns to the maximum of the range.
Dosing mode: LOW
ppm
H ysteresi s
Se t p o i n t
Status
Relay
Op e n
Cl o se
Figure 2 Relay setpoint menu
It is the choice to decrease the measurement's value when it rises above a chosen value.
The relay closes when the measurement value is beyond the maximum of the range and it opens
when it returns to the minimum of the range