Descargar Imprimir esta página

Sime MURELLE 70 BOX ErP Manual De Instrucciones página 42

Ocultar thumbs Ver también para MURELLE 70 BOX ErP:

Publicidad

Idiomas disponibles

Idiomas disponibles

2
INSTALLATION
Installation.is.permanent.and.must.exclu-
sively. be. performed. by. specialised. and.
qualified. personnel,. following. all. the.
instructions.and.provisions.included.in.this.
manual.. Current. regulations. must. also.
be.met.
2.1
SUPPLY (fig. 4)
MURELLE EQUIPE 70-105 BOX ErP heat.
modules,. inter-connectible. by. flange,. are.
supplied.with.an.external.pre-painted.zinc-
coated.laminate.case..
They. are. complete. with. supply/return.
water.manifold.fastening.screws.and.mani-
fold. gas,. external. temperature. probe. kit,.
cascade. supply. and. RS-485. code. 8092250.
board.connection.cable.
Available.separately:
–. Tubes.connecting.the.hydraulic.separa-
tor.kit.code.8101534.for.left-hand.fixtu-
res.for."70-105 BOX ErP".
–. Single. box. (size:. 630. x. 640. x. 1600). for.
hydraulic.separator,.code.8101517.(figu-
re.4).
–. Hydraulic.separator.kit.code.8101550.for.
NOTICE: The supply and return of the hydraulic compensator can be positio-
ned on the right or left-hand side of the box by moving the connection flange
secured with six screws.
42
"70-105 BOX ErP".
–. Polypropylene. exhaust. manifold. kit. for.
indoor.installation.(purposely.treated.to.
resist.weathering.when.installed.outdo-
ors):
. code.8102511.for."70 BOX ErP" module
. code.8102512.for."105 BOX ErP" module
–. Exhaust. terminal. code. 8089530. for.
outdoor.installations.
To.electrically.connect.the.modules.and.to.
assemble.the.exhaust.for.indoor.or.outdoor.
installations,.see.points.2.6,.2.7.and.2.10.in.
260
415
this.manual.
67 5
2.2
INSTALLATION
2.2.1
Indoors
MURELLE EQUIPE 70-105 BOX ErP. heat.
modules. can. be. installed. in. boiler. rooms.
whose.size.and.requirements.meet.current.
regulations..
Furthermore,. vents,. with. surface. areas. at.
least..3.000.sq..cm..or..5.000.sq..cm.for.gas.
SINGLE BOX FOR
BOX CONTENITORE SINGOLO
HYDRAULIC SEPARATOR AND TUBES CONNECTING
PER SEPARATORE IDRAULICO
code 8101517
cod. 8101517
45
630
1100
630
1730
403
64 0
with. density. over. 0.8,. must. be. installed. in.
the.outer.walls.for.room.ventilation..
90
2.2.2
Outdoors
S3
MURELLE EQUIPE 70-105 BOX ErP. heat.
modules. can. also. be. installed. outdoors.
G
with.the.specific.exhaust.for.single.module.
code.8089530.
15 5
2.3
SYSTEM CONNECTIONS
To.protect.the.heat.system.from.damaging.
corrosion,. incrustation. or. deposits,. after.
installation. it. is. extremely. important. to.
clean. the. system. using. suitable. products.
such. as,. for. example,. Sentinel X300 (new
systems), X400 and X800 (old systems) or
Fernox Cleaner F3..
Complete. instructions. are. provided. with.
the. products. but,. for. further. informa-
tion,. you. may. directly. contact. SENTINEL.
PERFORMANCE. SOLUTIONS. LTD. or.
FERNOX.COOKSON.ELECTRONICS..
For.long-term.protection.agains.corrosion.
R
403
64 0
Fig..4

Publicidad

loading

Este manual también es adecuado para:

Murelle 105 box erpMurelle 35 box erp