Menu 5: Basic switchgear settings
No.
Description
Parity
5.1.2.3
Values: even, non, odd
Factory setting: even
Stop bits
5.1.2.4
Values: 1, 2
Factory setting: 1
BACnet instance device ID
5.1.2.5
Value range: 0 to 9999
Factory setting: 128
5.1.3.0 GSM**
5.2.0.0 Sensor settings
Measurement range
5.2.1.0
Value range: 0 to 12.50
Factory setting: 2.50
Sensor type
Values: 0 – 10 V, 2 – 10 V,
5.2.2.0
0 – 20 mA, 4 – 20 mA
Factory setting: 4-20mA
Priority when dry run and high
water signals are present simul-
5.2.5.0
taneously**
Values: Dry Run, High Water
Factory setting: Dry Run
Signal detection for level control:
5.2.6.0
Sensor
5.4.0.0 Limit values
Dry run level
5.4.1.0
Value range*: 0.01 to 12.39
Factory setting: 0.12
High water alarm level
5.4.2.0
Value range*: 0.12 to 12.50
Factory setting: 1.50
High water alarm delay
5.4.4.0
Value range: 0 to 30
Factory setting: 0
Running time monitoring of indi-
vidual pumps
5.4.5.0
Values: ON, OFF
Factory setting: ON
Max. running time of individual
pumps
5.4.6.0
Value range: 0 to 60
Factory setting: 15
36
Menu 5: Basic switchgear settings
Display
No.
Behaviour in case of mains con-
nection errors**
5.4.7.0
Values: OFF, Message, Stop
Pumps
Factory setting: Stop Pumps
Behaviour on activation of ther-
mal motor winding monitoring
5.4.8.0
and leakage detection**
Values: Auto Reset, Manu Reset
Factory setting: Auto Reset
Behaviour when "External OFF"
contact is open**
5.4.9.0
Values: Ext.Off, Alarm
Factory setting: Ext. off
5.5.0.0 Setting for signal outputs
Collective run signal (SBM)**
function
5.5.1.0
Values: Ready, Run
Factory setting: Run
Collective fault signal function**
5.5.2.0
Values: Fall, Raise
Factory setting: Raise
5.6.0.0 Pump cycling
General pump cycling
5.6.1.0
Display: ON
Pump cycling after time interval
5.6.2.0
Display: OFF
* The value range is dependent on the sensor
measuring range!
** See the function description below
6.5.2. Explanation of individual functions and settings
Menu 5.1.3.0 / GSM
This menu item is only active if the optionally
available module has been installed in the switch-
gear. Please contact Wilo customer service for
more information and for retrofi tting.
Menu 5.2.5.0 / Priority when dry run and high
water signals are present simultaneously
If the system malfunctions, it may happen that
both signals are present at the same time. In such
cases, it is necessary to stipulate which signal is
overriding:
• "Dry Run" Dry-running protection
• "High Water": High water alarm
OPERATION AND FUNCTION
Description
Display
WILO SE 08-2016 V05 DIN A4