SICK GTE2 Flat Manual De Instrucciones página 9

Ocultar thumbs Ver también para GTE2 Flat:

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 15
5.1
Notes on UL approval
6
Commissioning
6.1
Alignment
6.2
Check the application conditions:
8025415.1HTH/2023-03-02 | SICK
Subject to change without notice
The device shall be supplied from an isolating transformer having a secondary overcur‐
rent protective device that complies with UL 248 to be installed in the field rated either:
a)
max 5 amps for voltages 0 ~ 20 V (0 ~ 28.3 V peak), or
b)
100 / Vp for voltages of 20 ~ 30 V (28.3 ~ 42.4 V peak).
Alternatively, they can be supplied from a Class 2 power supply.
UL Environmental Rating: Enclosure type 1
Alignment
Figure 2: Alignment
Sensing range
1
1.5 2
2
3
3.5
9
3
3.5/4.5
6
7
4
8
0
(0.16)
(0.31)
Sensing range
Sensing range typ. max.
Figure 4: Sensing range 15 mm
Figure 3: Alignment 2
12.5
15
11
12
16
(0.47)
(0.63)
Distance in mm (inch)
O P E R A T I N G I N S T R U C T I O N | GTE2 Flat
OPERATING INSTRUCTION
en
9