Εnglish
A5E41143699-AB
Wiring the TM-IM/EM, TM-EM/EM terminal submodule
• When laying the cable and connecting the submodule,
observe the regulations in EN 60 079-14 plus any
applicable national regulations.
• In wiring the submodule, you must strictly separate the
intrinsically safe lines from the non-intrinsically safe. They
must be laid in separate cable ducts.
• Sensors from Zone 0, Zone 1, Zone 2 as well as Zone 20,
Zone 21, Zone 22 and the secured area may be connected
to the terminal submodule. The electronic submodule's
terminal assignment can be found in the manual
"SIMATIC ET 200iSP Distributed I/O".
• The safety data (maximum values) for the sensor/actuator
must be adjusted to the electronic submodule's
corresponding maximum values. The maximum values of
the sensor/actuator can be found in the associated Ex
certificates. In accordance with EN 60 079-14, the
following are valid:
U
≤ U
; I
≤ I
; P
≤ P
; C
≥ C
+ C
; L
0
i
0
i
0
i
0
i
Line
Εnglish
≥ L
+ L
0
i
Line