Technical data
3.3
Installing the Polytron 7000 with LON
Interface
With LON communication, up to 63 Polytron 7000 can be connected
as bus, star, ring or mixed to a 4-wire cable (Fig. G).
CAUTION
!
If installed in 4-wire technology, the transmitter has no
explosion protection. The transmitter must not be installed in
explosion-hazard areas! Explosion hazard!
1. Install the 4-wire connection cable in the cable gland, cut to length
and strip ends (approx. 80 mm).
2. Shorten any shielding present so short-circuits cannot occur.
3. To connect the cable: Fix in the terminals on the 4-pin connection
terminal – observe polarity (Fig. E, item 1).
4. Push the connection terminal back into the holder.
5. Fix cable in mount.
6. Replace the rain cover (dust and rain protector).
20
4
Technical data
Cable type
at least 2-wire cable
Conductor cross-
2
0.5 mm
section
Cable entry
M20 x1.5 for cable diameters 6 mm to 12 mm
5
Order list
Designation and description
Dräger Docking Station
Mounting support
4-pin connection terminal for the
Polytron 7000
Middle connection terminal
Safety Barrier Zone 2
Dräger Docking Station for Polytron 3000/7000
2
(AWG 20) to 2.5 mm
(AWG 13)
Order no.
83 17 990
68 09 772
83 16 268
83 16 422
83 23 873