INSTALLATIoN
electrical connection
HSBC 180 S Plus: Electrical connection single phase
Xd02
electric emergency/booster heater (dHC)
Connected
Cable
load
cross-sec-
tion
2,9 kW
2.5 mm²
5,9 kW
2.5 mm²
2.5 mm²
f Connect the cables for the electrical emergency/booster
heater with the desired rating as in the table.
Control voltage
Material losses
!
f Only connect energy efficient circulation pumps ap-
proved by us to the pump connections.
Xd01.2
Heat pump enable signal
EVU
Enable signal, bus cable to the WPM screened with
strain relief in terminal.
Heat pump manager terminal assignment
WARNING Electrocution
Only components that operate with safety extra low
voltage (SELV) and that ensure secure separation from
the mains voltage supply may be connected to the low
voltage terminals of the appliance.
Connecting other components can make parts of the ap-
pliance and connected components live.
f Only use components which have been approved by
us.
www.stiebel-eltron.com
Terminal assignment
PE
N
L
PE
N
L
PE
N
L
Safety extra low voltage
X1.1
+
+
CAN (connection for heat pump and WPE heat
CAN A
-
-
pump extension)
L
L
H
H
X1.2
+
+
CAN (connection for FET remote control and
CAN B
-
-
ISG Internet Service Gateway)
L
L
H
H
X1.3
Signal
1
Outside sensor
Earth
2
X1.4
Signal
1
Buffer sensor (heating circuit sensor 1)
Earth
2
X1.5
Signal
1
Flow sensor
Earth
2
X1.6
Signal
1
Heating circuit sensor 2
Earth
2
X1.7
Signal
1
Heating circuit sensor 3
Earth
2
X1.8
Signal
1
DHW cylinder sensor
Earth
2
X1.9
Signal
1
Source sensor
Earth
2
X1.10
Signal
1
2nd heat generator (2.WE)
Earth
2
X1.11
Signal
1
Cooling flow
Earth
2
X1.12
Signal
1
DHW circulation sensor
Earth
2
X1.13
Signal
1
FE7 remote control / telephone remote
Earth
2
switch / heating curve optimisation / SG Ready
Signal
3
X1.14
Constant 12 V
+
Analogue input 0-10 V
Input
IN
GND
X1.15
Constant 12 V
+
Analogue input 0-10 V
Input
IN
GND
X1.16
Signal
1
PWM output 1
Earth
2
X1.17
Signal
1
PWM output 2
Earth
2
X1.18
+
+
CAN (FES)
CAN B
-
-
L
L
H
H
X1.19
+
+
CAN (connection for heat pump and WPE heat
CAN A
-
-
pump extension)
L
L
H
H
Mains power supply
X2.1
L
L
L
L
N
N
PE
X2.2
L' (power supply
L'
utility input)
L* (pumps L)
L* (pumps L)
HSBC 180 Plus | HSBC 180 S Plus |
Power supply
L' (power supply utility input)
L* (pumps L)
39