Technical data
General data
The table below shows the general technical data:
Data
Range - humidity
%RH hysteresis
Range - temperature
Mains connection
Max. ampere rating
Max. input power
Air production
Coolant
Coolant filling
GWP (Global Warming Potential
Noise level at 1 m distance
Weight
Protection class
Filter
kWh measuring accuracy
EU declaration of
Dantherm Air Handling A/S, Marienlystvej 65, DK-7800 Skive declares herewith that the
compliance
following product:
Dehumidifier, type CDT 90 MKII, item number 351194:
which is covered by this declaration, complies with the following directives:
- and has been manufactured in accordance with the following harmonised standards:
Skive, 28.08.2012
15
2006/42/EC
The Machine Directive
2006/95/EC
The Low Voltage Directive
2004/108/EC
The EMC Directive
2004/12/EC
The Packaging Directive
2002/95/EEC
The RoHs Directive
2002/96/EC
The WEEE Directive
EN 12100:2010
Machine Safety
EN 60 335-1:2012
Low Voltage Safety
EN 60 335-2-40:2003 Low Voltage Safety
EN 61 000-6-2:2005 EMC
EN 61 000-6-3:2007 Emissions
unit
CDT 90
%RH
40-100
%RH
°C
3-32
V/Hz
230/50
A
7.2
kW
1.64
m
/h
1000
3
-
R407C
kg
1.6
-
1653
dB
62
kg
62
IP
x4
PPI
15/G1
%
±5%
4

Publicidad

loading