Descargar Imprimir esta página

Toshiba Carrier MMK-AP0307HPUL Manual De Instalación página 37

Publicidad

Idiomas disponibles

Idiomas disponibles

Check code
Wired
Outdoor unit 7-segment display
remote
controller
Auxiliary code
display
#0: Element short circuit
#E: Vdc voltage trouble
#1: Position detection circuit trouble
#2: Input current sensor trouble
#3: Motor lock trouble
#C: Sensor temperature trouble
P22
P22
(No TH sensor)
#4: Motor current trouble
#D: Sensor short circuit/release
trouble (No TH sensor)
#5: Synchronization/step-out trouble
*Put in Fan Inverter No. in [#] mark.
01: Comp. 1 side
P26
P26
02: Comp. 2 side
03: Comp. 3 side
01: Comp. 1 side
P29
P29
02: Comp. 2 side
03: Comp. 3 side
P31
*1 Inverter quantity information
(Super Modular Multi System i series (SMMS-i))
Comp. Inverter
Fan
No.
Inverter
1
2
3
01
Comp. 1
02
Comp. 2
03
Comp. 1 + Comp. 2
04
Comp. 3
05
Comp. 1 + Comp. 3
06
Comp. 2 + Comp. 3
07
Comp. 1 + Comp. 2 + Comp. 3
08
Fan
09
Comp. 1 + Fan
0A
Comp. 2 + Fan
0B
Comp. 1 + Comp. 2 + Fan
0C
Comp. 3 + Fan
0D
Comp. 1 + Comp. 3 + Fan
0E
Comp. 2 + Comp. 3 + Fan
0F
All
: Inverter trouble
• For details about check codes determined with an Interface P.C. board or an Inverter P.C. board, refer to the Installation Manual of the outdoor unit.
Trouble detected by central control device
Check code
Central
Outdoor unit 7-segment display
control
device
Auxiliary code
indication
C05
C06
C12
Differs according to trouble contents of unit with occurrence of alarm
P30
(L20)
Wireless remote controller
Sensor block display of
receiving unit
Operation Timer Ready Flash
Trouble
Wireless remote controller
Sensor block display of
receiving unit
Operation Timer Ready Flash
(L20 is displayed.)
– 36 –
Check code name
ALT
Outdoor unit fan inverter trouble
ALT
IPM short protection trouble
Comp. position detective circuit system
ALT
trouble
Other indoor unit trouble
ALT
(Group follower indoor unit trouble)
*1 Inverter quantity information
(Super Modular Multi System e series (SMMS-e))
Comp.
Fan
Inverter
Inverter
No.
1
2
1
01
02
03
08
09
0A
0B
10
11
12
13
18
19
1A
1B
: Inverter trouble
Check code name
Sending trouble in central control device
Receiving trouble in central control device
Batch alarm of general-purpose equipment
control interface
Group control follower unit trouble
• Duplication addresses of indoor units in
central control device
• With the combination of air conditioning
system, the indoor unit may detect the
check code of L20
Installation Manual
Judging
device
Inverter
Inverter
Inverter
Indoor unit
Trouble
2
Comp. 1
Comp. 2
Comp. 1 + Comp. 2
Fan1
Comp. 1 + Fan1
Comp. 2 + Fan1
Comp. 1 + Comp. 2 + Fan1
Fan2
Comp. 1 + Fan2
Comp. 2 + Fan2
Comp. 1 + Comp. 2 + Fan2
Fan1 + Fan2
Comp. 1 + Fan1 + Fan2
Comp. 2 + Fan1 + Fan2
All
Judging
device
Communication
Communication
General-purpose
equipment I/F
Communication
EN
Link
Link
Link
36-EN

Publicidad

loading

Este manual también es adecuado para:

Carrier mmk-ap0367hpul