Descargar Imprimir esta página

Toshiba MMC-AP0158HP Serie Manual De Instalación página 21

Publicidad

Idiomas disponibles

Idiomas disponibles

10
Maintenance
<Daily maintenance>
▼Cleaning of air fi lter
• If
is displayed on the remote controller, maintain
the air fi lter.
1
Push the
button to stop the operation,
then turn off the circuit breaker.
8
2
Open the air intake grille.
• Remove the screws of air intake grille fi xing
knob on a side of each fi lter.
• Slide the air intake grille fi xing knobs (two
positions) toward the arrow direction (OPEN),
and then open the air intake grille.
Air intake grille
Air intake grille fi xing knob
Air fi lter
3
Take out air fi lter.
• Push the handle of the air fi lter, and remove the
hook of the air intake grille. Pull out the air fi lter
toward you.
Air fi lter
Air fi lter handle
Air intake grille hook
Air fi lter handle
Air intake grille fi xing hook
39-EN
4
Cleaning with water or vacuum cleaner.
• If dust is heavy, wash it with tepid water
including neutral detergent or water.
• After cleaning with water, dry it completely in the
shade.
5
Mount the air fi lter.
1, 7
6
Close the air intake grille.
• Close the air intake grille, and then fi x it securely
while sliding knob closed side (CLOSE).
• Fix the screws of air intake grille fi xing knob on a
side of each fi lter.
Air intake grille fi xing knob
Air fi lter
7
Turn on the circuit breaker, then push the
button on the remote controller to start
the operation.
8
After cleaning, push
.
display disappears.
CAUTION
• Do not start the air conditioner while leaving air fi lter
removed.
• Push the fi lter reset button. ( indication will be turn
off.)
▼Periodic Maintenance
• For environmental conservation, it is strongly recommended that the indoor and outdoor units of the air
conditioner in use be cleaned and maintained regularly to ensure effi cient operation of the air conditioner. When
the air conditioner is operated for a long time, periodic maintenance (once a year) is recommended. Furthermore,
regularly check the outdoor unit for rust and scratches, and remove them or apply rustproof treatment, if
necessary.
As a general rule, when an indoor unit is operated for 8 hours or more daily, clean the indoor unit and outdoor unit
at least once every 3 months. Ask a professional for this cleaning / maintenance work. Such maintenance can
extend the life of the product though it involves the owner's expense.
Failure to clean the indoor and outdoor units regularly will result in poor performance, freezing, water leakage, and
even compressor failure.
Inspection before maintenance
Following inspection must be carried out by a qualifi ed installer or qualifi ed service person.
Parts
Heat exchanger
Fan motor
Fan
Filter
Drain pan
▼Maintenance List
Part
Heat exchanger
Air intake grille
Fan motor
Filter
Fan
Air intake /
discharge grilles
Drain pan
Ornamental panel,
louvres
Exterior
– 20 –
Inspection method
Look through the air discharge port to check the part. Examine the heat exchanger if there
is any clogging or damages.
Check if any abnormal noise can be heard.
Check if any abnormal noise can be heard.
Go to installed location and check if there are any stains or breaks on the fi lter.
Look through the air discharge port to check the part. Check if there is any clogging or drain
water is polluted.
Unit
Check (visual / auditory)
Indoor / outdoor
Dust / dirt clogging, scratches
Indoor / outdoor
Sound
Indoor
Dust / dirt, breakage
• Vibration, balance
Indoor
• Dust / dirt, appearance
Indoor / outdoor
Dust / dirt, scratches
Dust / dirt clogging, drain
Indoor
contamination
Indoor
Dust / dirt, scratches
• Rust, peeling of insulator
Outdoor
• Peeling / lift of coat
Maintenance
Wash the heat exchanger when it is
clogged.
Take appropriate measures when
abnormal sound is generated.
• Wash the fi lter with water when it is
contaminated.
• Replace it when it is damaged.
• Replace the fan when vibration or
balance is terrible.
• Brush or wash the fan when it is
contaminated.
Fix or replace them when they are
deformed or damaged.
Clean the drain pan and check the
downward slope for smooth drainage.
Wash them when they are
contaminated or apply repair coating.
Apply repair coating.
40-EN

Publicidad

loading