2.1.
Rear view panel
PH 8010 (1K)
1.
AC Input
| 2.
Input circuit breaker
5. SNMP inteligent slot (option) | 6. External battery conector (Only available for L model)
7. Output receptacles | 8. Output terminal | 9. Output circuit breaker
2.2. Setup the UPS
Step 1: UPS input connection
• Plug the UPS into a two-pole, three-wire, grounded receptacle only. Avoid using extension cords.
• For 200/208/220/230/240VAC models: The power cord is supplied in the UPS package.
• For 100/110/115/120/127VAC models: The power cord is attached to the UPS. The input plug is a NEMA 5-15P for 1K
model and NEMA 5-20P for 2K model.
Step 2: UPS output connection
• For socket-type outputs, simply connect devices to the outlets.
• For terminal-type input or outputs, please follow below steps for the wiring configuration:
a) Remove the small cover of the terminal block
b) Suggest using AWG14 or 2.1mm2power cordsfor 3KVA (200/208/220/230/240VAC models). Suggest using AWG12-10
or 3.3mm2-5.3mm2power cords for 3KVA (100/110/115/120/127VAC models). Please also install a circuit breaker (40A)
between the mains and AC input of UPS in 3KVA (100/110/115/120127VAC models) for safety operation.
c) Upon completion of the wiring configuration, please check whether the wires are securely affixed.
d) Put the small cover back to the rear panel.
Segurança e harmonia
ININTERRUPTA
PH 8020 (2K)
| 3.
USB communication port
2. Installation and setup
| 4.
RS-232 communication port
PH 8010 | PH 8020 | PH 8030
Uninterruptible Power Supply
EN
PH 8030 (3K)
35