3.1. Button operation
Button
ON/Mute Button
OFF/Enter Button
Select Button
ON/Mute + Select
Button
Segurança e harmonia
ININTERRUPTA
• Turn on the UPS: Press and hold ON/Mute button for at least 2 seconds to turn on
the UPS.
• Mute the alarm: When the UPS is on battery mode, press and hold this button for at
least 5 seconds to disable or enable the alarm system. But it's not applied to the
situations when warnings or errors occur.
• Up key: Press this button to display previous selection in UPS setting mode.
• Switch to UPS self-test mode: Press ON/Mute buttons simultaneously for 5 seconds
to enter UPS self-testing while in AC mode, ECO mode, or converter mode.
• Turn off the UPS: Press and hold this button at least 2 seconds to turn off the UPS in
battery mode. UPS will be in standby mode under power normal or transfer to
Bypass mode if the Bypass enable setting by pressing this button.
• Confirm selection key: Press this button to confirm selection in UPS setting mode.
• Switch LCD message: Press this button to change the LCD message for input
voltage, input frequency, battery voltage, output voltage and output frequency. It will
return back to default display when pausing for 10 seconds.
• Setting mode: Press and hold this button for 5 seconds to enter UPS setting mode
when UPS is in standby mode or bypass mode.
• Down key: Press this button to display next selection in UPS setting mode.
• Switch to bypass mode: When the main power is normal, press ON/Mute and Select
buttons simultaneously for 5 seconds. Then UPS will enter to bypass mode. This
action will be ineffective when the input voltage is out of acceptable range.
Function
PH 9310 | PH 9315 | PH 9320 | PH 9330
Uninterruptible Power Supply
3. Operations
EN
43