3. Installation and Setup
5) Remove the terminal block cover to access the UPS system's input, output and grounding connection terminals. Then connect the
wires according to the terminal block diagram shown below. Connect the grounding/earthing wires first when making other wire
connections.
Notes:
• Ensure the wires are tightly and securely connected to the terminals.
• Install the output breaker between the output terminal and the load. The breaker should be qualified with leakage current protective function.
• Cabling should be protected by flexible conduit and routed through the appropriate knockouts in the terminal block cover.
Output
Single Input Terminal Block Wiring Diagram for S3M30KX and S3M40KX
Output
Dual Input Terminal Block Wiring Diagram for S3M30KXD and S3M40KXD
Note: Be sure to also add an equipotential bonding wire between the UPS and the External Battery Cabinets.
6) Re-attach the terminal block cover to the rear panel of the UPS.
Input
Input 2
Input
BAT+
PBAT
PBAT
NBAT
NBAT
±240V Battery Connection Wiring
Input
Single Input Terminal Block Wiring Diagram for S3M60K and S3M80K
UPS INPUT~
Input
Dual Input Terminal Block Wiring Diagram for S3M60KXD and S3M80KXD
BAT-N
BAT-
TO UPS BAT+
TO UPS BAT+
TO UPS BAT N
TO UPS BAT N
TO UPS BAT-
TO UPS BAT-
23
Output
Output
~OUTPUT
~OUTPUT
~BYPASS INPUT
~BYPASS INPUT
Input 2