Descargar Imprimir esta página

Tripp-Lite SmartOnline S3M30KXD Manual Del Propietário página 39

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 55
4. Operation
15: Inverter-A Voltage Adjustment
Interface
16: Inverter-B Voltage Adjustment
Interface
17: Inverter-C Voltage Adjustment
Interface
18: Output-A Voltage Calibration
Interface
19: Output-B Voltage Calibration
Interface
Setting
Parameter 2: Choose Add or Sub to adjust inverter-A voltage.*
Parameter 3: The voltage range is 0V to 9.9V. The default value is 0V.
* Add or Sub is according to the output voltage that you set.
Setting
Parameter 2: Choose Add or Sub to adjust inverter-B voltage*.
Parameter 3: The voltage range is 0V to 9.9V. The default value is 0V.
*It will display number 1 under
Setting
Parameter 2: Choose Add or Sub to adjust inverter-C voltage*.
Parameter 3: The voltage range is 0V to 9.9V. The default value is 0V.
*It will display number 2 under
Setting
Parameter 2: Always shows OP.V as output voltage.
Parameter 3: Shows the internal measurement value of the output-A voltage. You can calibrate
it by pressing Up or Down according to the measurement from an external voltage meter. The
calibration result will be effective by pressing Enter. The calibration range is limited within +/-9V.
This function is normally used for parallel operation.
Setting
Parameter 2: Always shows OP.V as output voltage*.
Parameter 3: Shows the internal measurement value of the output-B voltage. You can calibrate
it by pressing Up or Down according to the measurement from an external voltage meter. The
calibration result will be effective by pressing Enter. The calibration range is limited within +/-9V.
This function is normally used for parallel operation.
OP.U
*It will display number 1 under
SUB
or
to represent inverter-B voltage.
SUB
or
to represent inverter-C voltage.
to represent the output B voltage.
39

Publicidad

loading