Maximum CI-200s per power pack: B series = 5, BZ series = 7. When
using more sensors than this, multiple power packs are required.
For all configurations—connect the low voltage:
• RED wire (+24VDC) from power pack to VIOLET wire on sensor.
• BLACK wire (Return) from power pack to GREEN wire on sensor.
Connections for the following configurations:
Single lighting load controlled by occupancy only—connect:
• BLUE wire from power pack to yellow wire on sensor.
Single lighting load controlled by occupancy, dependent on light
level (ambient light)—connect:
• BLUE wire from power pack to blue wire on sensor.
One lighting load for occupancy control, and a second load for
occupancy and light level (ambient light) control—connect:
• BLUE wire from power pack to yellow wire on sensor.
• BLUE wire from auxiliary pack to blue wire on sensor.
• BLACK wire from auxiliary pack to gray wire on sensor.
Isolated Relay
(The Isolated Relay is rated for 1A @24VDC or 24VAC) Connect the wires necessary to the application that requires this output.
• RED (Common) (must be used for proper operation)
• BROWN (Normally Closed)—Open when occupancy is detected.
• ORANGE (Normally Open)—Closed when occupancy is detected.
The sensor comes factory preset and ready for operation. If testing of operation is
desired:
• Remove the sensor's cover (twist).
• Refer to the DIP switch settings chart for switch configurations.
• Make sure that office furniture and fixtures are in place.
1. Restore power to the lighting circuits and turn the lights on.
• There is a one minute warm-up when power is initially restored to the sensor
before the sensor works properly.
2. For testing, set the Time Delay to minimum (15 secs.).
3. Set Sensitivity to maximum.
4. Turn Light Level Adjustment trimpot to maximum.
5. Replace the sensor's cover then move away from sensor and be still. The
lights should go off after 15 seconds. If lights remain on, see Unwanted Sensor
Activations under Troubleshooting. With movement in the area, the lights should
turn back on.
6. If using the light level feature (otherwise skip to step 7), turn the adjustment
trimpot to minimum, and repeat step 5. Unless it is very dark, when the lights
turn off, the lights controlled by light level should not turn back on even with
movement in the area. Until ready to make the final adjustment, leave the setting
at maximum. The controlled lights will then not be affected by ambient light levels.
To make the light level adjustment: (The final light level setting for normal
operation should be made at a time when, with the lights off, the ambient light level
is at the point where it is desired for the lights to turn on.)
Set the Time Delay and the Light Level to minimum, then be still until the lights turn
off (about 15 seconds). Slowly turn the light level adjustment toward maximum until
the lights turn on—then turn it back slightly. At this setting the lights will not turn on
if ambient light levels are above the current level.
7. Set the desired Time Delay for operation (DIP switches #1 – 6). Factory preset
Time Delay is 20 minutes; other suggestions are:
Offices and conference rooms (10 minutes), Classrooms (10 minutes),
Warehouses (6 minutes), Hallways (4 minutes).
Service Mode
To override all sensor functions, set DIP switch 6 to the OFF position. The red LED will
come on and stay on for the duration of the override.
WIRING DIRECTIONS
SENSOR ADJUSTMENT
3