Features
C13
Outlets: During normal operation, the outlets distribute AC power to connected equipment.
Note: PDU3VN6G60C does not include C19 receptacles.
Note: NEMA 5-15/20R receptacles are only included with the PDU3VN6L2120/PDU3VN6L2130 models.
Bank Status LED
Push-to-Reset Guard
15-09-467-9332F9.indb 16
C19
Bank Status LED: Once the unit is powered on, each Bank Status LED
will illuminate when the associated bank is ready to distribute live AC
power.
LED Color
LED Status
Green
On
Yellow
On
Red
Off
Flashing Red
Off
Off
Off
Note: Colors noted here reflect standard LED configuration. See chart on page 14
for full LED color definitions.
Circuit Breaker (Select Models): Each Load Bank is protected by a
circuit breaker. If the connected equipment load exceeds the Maximum
Load Rating for those banks of the PDU, the circuit breaker will trip.
Disconnect excess load and reset the breaker.
Note: Each breaker comes equipped with a push-to-reset guard to prevent
accidental breaker tripping. To turn off the breaker, insert a flathead screwdriver into
the reset slot.
Note: PDU3VN6L2120 and PDU3XVN6G20 do not include breakers.
Mounting Brackets: Use these brackets as an alternate PDU mounting
method.
Mounting Buttons: Come pre-installed on the back side of the PDU and
are used for toolless mounting. Note: Four additional mounting buttons
are included for alternate rack styles.
PDUMVROTATEBRKT Mounting Accessory: Use these V-shaped
brackets to mount the PDU with its outlets facing the rear of the rack.
16
NEMA 5-15/20R
Comments/Notes
Normal operation.
Bank's current has exceeded 80% of its current
rating.
Bank's voltage is below the Low Voltage
threshold.
Circuit breaker for this bank has tripped.
Bank is powered off.
10/5/2015 11:41:38 AM