Installer setup (ISU)
1 Press and hold Menu (center) for
approximately 3 seconds to enter menu.
2 Press Edit ( ) to change values within a
setup option.
3 Press Next ( ) to advance to the next setup
option.
4 Press Done to Save and return to the main
menu screen.
NOTE: To keep the factory default settings,
press
to advance through the setup options.
Once you pass the last option, the thermostat
will automatically save and return you to the
main menu.
NOTE: A complete list of all setup (ISU)
parameters and options starts below and
continues through page 7.
Installer setup options (ISU)
NOTE: Depending on system settings, not all options may be available.
# ISU
ISU Name
125
Temperature Indication Scale
200
Heating System Type
205
Heating Equipment Type
218
Reversing Valve O/B
ISU Options (factory default in bold)
0 = Fahrenheit
1 = Celsius
1 = Conventional Forced Air Heat
2 = Heat Pump (TH1110D only)
3 = Radiant Heat
5 = None (Cool Only)
Note: This option selects the basic system type your thermostat will
control.
Conventional Forced Air Heat:
1 = Standard Efficiency Gas Forced Air
2 = High Efficiency Gas Forced Air
3 = Oil Forced Air
4 = Electric Forced Air
5 = Hot Water Fan Coil
Heat Pump:
7 = Air to Air Heat Pump
8 = Geothermal Heat Pump
Radiant Heat:
9 = Hot Water Radiant Heat
12 = Steam
Note: This option selects the equipment type your thermostat will control.
Note: This feature is NOT displayed if feature 200 is set to Cool Only.
0 = O (O/B in Cool)
1 = B (O/B in Heat)
Note: This option is only displayed if the Heat Pump configured. Select
whether reversing valve O/B should energize in cool or in heat.
6
+
+