Diameters and max. lengths of the cable for direct start:
Motor version
DM
3~ 50 Hz 400 V
3~ 60 Hz 480 V
Cable weight (kg/m)
Diameters and max. lengths of the cable (6" motors) for star-delta start:
Motor version
DM
3~ 50 Hz 400 V
3~ 60 Hz 480 V
Cable weight (kg/m)
1~ 230 V (50 Hz, 60 Hz), EM version (Fig. 1)
Capacity
Current consump-
tion 230V
kW
A
0.37
3.2
0.55
4.3
0.75
5.3
1.10
7.8
1.50
9.9
2.20
14.9
3~400 V 50 Hz, 3~480 V 60 Hz, DM version
(Fig. 2 / 3)
Capacity
kW
0.37
0.55
0.75
1.10
1.50
2.20
3.00
3.70
4.00
5.50
7.50
9.30
11.00
15.00
18.50
14
Motor
Cable
kW
4 x 1.5 mm²
4 x 2.5 mm²
9.30
32
54
11.00
--
45
15.00
--
--
18.50
--
--
22.00
--
--
30.00
--
--
37.00
--
--
45.00
--
--
0.20
0.25
Motor
Cable
kW
4 x 1.5 mm²
4 x 2.5 mm²
2.20
182
304
3.00
141
236
3.70
115
192
4.00
106
177
5.50
79
131
7.50
58
98
9.30
48
81
11.00
40
68
15.00
30
50
18.50
24
41
22.00
--
34
30.00
--
--
37.00
--
--
45.00
--
--
0.20
0.25
Operating capacitor
μF
16
20
30
40
50
75
Current consumption400/480 V
A
1.3
1.7
2.2
3.2
4.0
5.9
7.8
9.1
10.0
13.7
18.0
20.3
23.3
31.3
38.5
4 x 4 mm²
4 x 6 mm²
87
130
72
109
54
81
44
66
--
55
--
--
--
--
--
--
0.30
0.40
4 x 4 mm²
4 x 6 mm²
486
730
378
567
307
461
283
425
210
316
157
235
130
195
109
163
81
121
66
99
55
83
40
60
--
50
--
--
0.30
0.40
Connections
(wire identification)
Fig. 1 - 3
a
black
b
blue / grey
c
brown
d
green/yellow
CAUTION! Danger of material damage!
Connecting the motor incorrectly can damage it!
• Check the mains voltage
• Do not cut the cable between the switchbox and
pump. The switchbox contains the necessary
motor capacitors (EM versions only).
• Fit ground
• Motor protection is regulated by a thermal or
magnetic switch (fitted on EM version, to be fitted
on the DM version)
8 Commissioning
8.1 Direction of rotation check (three-phase
motors only, the direction of rotation cannot be
confused on single-phase motors)
In order to define the correct direction of rotation,
it suffices to check the water pressure on the
pressure side of the pump that is running.
4 x 10 mm²
4 x 16 mm²
217
348
181
291
135
216
110
176
92
147
67
108
--
89
--
73
0.65
0.85
4 x 10 mm²
4 x 16 mm²
1217
1947
945
1513
768
1229
708
1133
527
843
392
628
326
522
272
436
203
324
165
264
138
221
101
162
83
134
68
109
0.65
0.85
WILO SE 10/2021