4.3 Enable Supervision of Wireless Zones

Each wireless device (excluding wireless keys) sends a supervisory signal periodically. If the receiver
does not receive a signal within the time programmed for the Wireless Supervisory Window, it
generates a supervisory fault.
NOTE: For wireless supervision to work, enable the wireless zone attribute on all wireless zones
(sections [101] to [164], option [8] ON).
To program the wireless supervisory window:
1. Enter [
][8][Installer Code] to access Installer Programming.
,
2. Enter [804] to access TR5164 Module Programming.
3. Enter section [081].
4. Enter the time period for the supervisory window. The window is programmed in 15 minute
increments. The default programming is:
• 96 (x15minutes), which is equal to 24 hours for the NA version, or
• 8 (x15minutes), which is equal to 2 hours for the EU version.
Valid entries are (4) to (96), equal to 1 to 24 hours.
5. To exit press [#].
NOTE: Supervision must be enabled for RF Delinquency.
To disable/enable zone supervision:
1. Enter [
][8][Installer Code] to access Installer Programming.
,
2. Enter [804] to access TR5164 Module Programming.
3. Enter sections [082]-[089]. Enable or disable supervision for each wireless zone by turning each
relevant option on or off. Supervision is enabled by default for all wireless zones.
4. To exit press [#].

4.4 Reporting Openings/Closings by Wireless Keys

Openings, closings and command output activation (e.g., opening a garage door) by individual
wireless keys can generate a system report on certain control panels.
To enable reporting for wireless key openings/closings:
1. Program a valid access code for each key (using [
NOTE: Program these access codes on the system after the TR5164 is connected to the
Keybus (Section 2.4, page 5). Access codes 17 – 32 are reserved for wireless keys 01-16
respectively. Refer to the alarm panel installation manual for information on access code
programming.
2. Program an opening and closing reporting code for each key ([339]-[340], [342]-[343]).
3. Turn off the Quick Arm option in section [015] option [4] of Installer Programming.
NOTE: To ensure that an unidentified wireless key cannot disarm the system, turn off
section [017], option [1] in Installer Programming.
][5] access code programming).
,
9