Electric Actuators Type EA04
► In addition to these instruction manual, also follow manufacturer›s specifications on ball valve type 546 Pro.
► Before installation, compare technical data of the actuator with the control and the valve. Only install actuator if the data match-
es.
► Before installation, check plugs and terminals for possible damage.
► Make sure that no damaged parts are used.
► Have installation and assembly only carried out by specialist staff.
► If device is directly controlled:
Fit a circuit breaker on site.
Do not connect grounding conductor
Requirements
Cross section of the power lines max. 1.5 mm2.
Fuse size: > 6 A.
► Ensure that actuator is only connected to voltages that meet the requirements on a protective extra low voltage circuit (PEVL).
► Connect actuator, see Section Connection diagram
4.2
Electrical connection
WARNING!
Too high current peaks the first time the actuator is switched on by charging the mains capacitor!
Danger of injury and/or malfunction.
► Connect actuator as per connection diagram and operate, see Section Connection diagram
WARNING!
Voltage too high!
Danger of injury and/or damage to property.
► Make sure that 24 V devices are only connected to voltages that meet the requirements of a safety extra low voltage circuit
(SELV).
NOTE!
Damage to the actuator by short circuit or corrosion!
Moisture and/or dirt in the actuator.
► Make sure that no water enters the actuator.
► Mount the cable routing, so it does not point upwards.
16