Electric Actuators Type EA04
5
Commissioning
Before commissioning the system, carry out a functional test of the product.
5.1
Functional test
Before actuator is connected to mains voltage:
► Make sure that main voltage matches details on type lable.
► Make sure that actuator is connected properly.
► Check fuse: > 6 A
► Check that valve position matches Position indicator of the actuator.
► Make sure that actuator and valve are connected correctly and tightly.
NOTE!
Using the manual emergency override, the actuator can open or close the valve even without mains voltage
WARNING!
Too high current peaks the first time the actuator is switched on by charging the mains capacitor!
Danger of injury and/ or malfunction.
► Connect actuator as per connection diagram and operate, see Section Connection diagram
WARNING!
Working with actuator cover removed!
Danger of injury and/ or material damage.
► Disconnect connections of the feed and control voltage.
► Only carry out adjustments on live parts with specially insulated tools.
18
Instruction manual