» Fig�15
1
Condensate discharge
8.4
CONNECTION FOR INTAKE OF FRESH AIR TO BE TREATED
The units are equipped with 3 fresh air inlets, positioned in the
corners. This air mixes with the air drawn in from the indoor en-
vironment and is then treated by the heat exchanger. (Fig.17 -
Fig.18 )
Ū The SPFAI1A (FWI-A 02-03-04) and SPFAI2A (FWI-A 06-07-08)
accessory is available: a fi tting for Ø100 pipe to be connect-
ed to the inlets located on the unit.
Ū It is necessary to fi lter the fresh air before introducing it in
the unit, making sure that its temperature is not too low.
Ū To avoid operating and noise-related problems, the fresh air
fl ow rate is limited to 20% of the unit's air fl ow at average
speed, with a maximum of 110 m
B
WARNING: It is necessary to prevent the intake of dust and
impurities that could foul the unit's exchanger.
» Fig� 17 FWI-A 02-03-04
/h for each intake.
3
» Fig�16
1
Condensate discharge
B
WARNING: The installation of the auxiliary water drip tray
is mandatory.
» Fig�18 FWI-A 06-07-08
I
III
II
IV