Standby mode
The control panel of the Geberit HS01 hygiene flush
EN
unit switches to standby mode after approx. 2 minutes
of inactivity and all LEDs will switch off.
1. Press any button to exit standby mode. The
current settings will be displayed.
2. Press the corresponding button to select the
desired function.
Setting the flush volume
The flush volume depends on the pipe length being
flushed and the DN pipe dimension. The following
table is used to calculate the flush volume.
A flush volume of 3 l is set at the factory. The
accuracy of the flush volume setting is +/- 10 % at
3 bar.
Table 1:
Pipe length
[m]
5
10
20
30
40
50
Calculating the flush volume
Flush volume [l]
DN12
1
2
3
5
5
7
DN15
1
2
4
7
10
15
DN20
2
3
7
10
15
20