Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

2. KIT COMPONENTS

2.1 AT-7000-R Receiver

The AT-7000-R Receiver detects the signal generated by the AT-7000-T transmitter along wires
using either the TIP SENSOR or SMART SENSOR and displays this information on the full color TFT
LCD display.
Active tracing using a signal generated by the AT-7000-T Transmitter
The SMART SENSOR works with a 6 kHz signal generated along energized wires (above 30V
AC/DC) and provides an indication of the wire position and direction relative to the receiver.
The SMART SENSOR is not designed to work on de-energized systems; for that application
the TIP SENSOR should be used in de-energized mode.
The TIP SENSOR may be used on either energized or de-energized wires and can be used for
general tracing, tracing in tight spaces, locating breakers, pinpointing wires in bundles or in
junction boxes. The TIP SENSOR mode will pinpoint the wire location with both an audible
and visual indication of detected signal strength, but unlike SMART SENSOR mode it will not
provide wire direction or orientation.
Note: The receiver will NOT detect signals from the wire through metal conduit or shielded
cable. Refer to Special Applications, section 4.4 "Tracing Wires In Metal Conduit" for
alternative tracing methods.
SMART SENSOR
(Back side)
NCV BUTTON
Non-Contact
Voltage mode
4-WAY
NAVIGATION KEYS
RUBBER OVER
MOLDED ENCLOSURE
Figure 1: Overview of AT-7000-R Receiver
HOT STICK ATTACHMENT POINT
(Do not use for voltage higher
than 600V)
6
TIP SENSOR
LCD DISPLAY
Full color TFT display
SENSITIVITY ADJUSTMENT
BUTTON (-/+)
ENTER BUTTON
Selects the functions
POWER BUTTON
Turns unit On / Off
BATTERY COMPARTMENT
(Back side)

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

At-7020At-7030At-7000-t

Tabla de contenido