Installation
If branch circuit to dryer is 15 feet (4.50 m) or
less in length, use U.L. (Underwriters
Laboratories) listed No. 10 A.W.G. wire (copper
wire only), or as required by local codes. If over
15 feet (4.50 m), use U.L. listed No. 8 A.W.G.
wire (copper wire only), or as required by local
codes. Allow sufficient slack in wiring so dryer
can be moved from its normal location when
necessary.
NOTE: The power cord (pigtail) is NOT supplied with the electric
dryer. Type of pigtail and gauge of wire must conform to local
codes and instructions.
The method of wiring the dryer is optional and subject to local
code requirements.
NOTE: Connect the dryer to the power supply with the
MAXIMUM RATED VOLTAGE listed on the nameplate.
120 ± 12
V.A.C.
240 ± 12
V.A.C.
NOTE: Use COPPER WIRE only.
Shorter than 15 ft. (4.5 m) use 10 A.W.G.
Longer than 15 ft. (4.5 m) use 8 A.W.G.
1
3-Wire Grounded Neutral 120/240 Volt, 60 Hertz
AC 1 Phase Service Entrance Switch Box
(Refer to NOTE above)
2
30 Ampere Fuses or Circuit Breaker
3
Neutral Wire
30
A Typical
INTERMEDIATE
30-Amp
FUSE BOX (May
Three-Wire
be omitted if
Receptacle
service entrance
NEMA Type
box is fused)
10-30R
WALL RECEPTACLE
120 ± 12
V.A.C.
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
The power cord (pigtail) connection between
wall receptacle and dryer terminal block IS NOT
supplied with dryer. Type of pigtail and gauge
of wire must conform to local codes and with
instructions mentioned on the following pages.
The method of wiring the dryer is optional and subject
to local code requirements. Refer to Figure 24.
POWER SUPPLY
L1
L2
PIGTAIL CONNECTION
4
Metallic or Non-Metallic Sheathed Cable
(Copper wire only)
5
Pigtail to Dryer (Refer to NOTE above)
6
Neutral
7
Terminal Block in Dryer
Figure 24
POWER SUPPLY
1
2
3
INTERMEDIATE
SHUT-OFF BOX
(May or may
not be fused)
4
5
6
7
L1
L2
DIRECT CONNECTION
D816I
801539