Troubleshooting
11
Troubleshooting
Problem
Cause
No cooling
The under-bench air conditioner is
capacity
not set to cooling.
The ambient temperature is above
52 °C.
The temperature set is higher than
the room temperature.
The ambient temperature is below
16 °C.
The thermal protection is defective.
The compressor is damaged.
The refrigerating agent filling is
insufficient.
The heat exchange coils are pol-
luted.
The external blower is defective.
26
FreshWell3000
Remedy
➤ Set the under-bench air
conditioner to cooling.
The under-bench air conditioner
is only designed for ambient
temperatures of up to 52 °C.
➤ Select a lower temperature.
The under-bench air conditioner
is only designed for ambient
temperatures above 16 °C.
➤ Contact an authorized service
agent.