Technical Data
Voltage
Voltage
Terminal wire area
Tightening torque
Current
- base I
b
- rated I
n
- reference I
ref
- maximum I
max
- minimum I
min
Frequency
Accuracy
Material
Operating temp.
Storage temp.
Humidity
Resistance to heat
Direct connected
57.7-288 V (-20% - +15%)
1 - 25 mm²
2.5 Nm
5 A
5 A
80 A
0.25 A
50 or 60 Hz ± 5%
1%, 2%
Polycarbonate in transparent front glass,
casing and terminal cover. Glass reinforced
polycarbonate in terminal block.
-40 °C - +70 °C
-40 °C - +85 °C
75% yearly average, 95% on 30 days/year
Terminal 960°C, cover 650°C (IEC 60695-
2-1)
5
Transformer conn.
0.5 - 10 mm²
2 Nm
1 A
1 A
6 A
0.02 A
50 or 60 Hz ± 5%
or 16,7 Hz (optional)
0.5%, 1%