8. TECHNICAL SPECIFICATIONS:
MultiPlus-II 48/3000/35-50 120 V
PowerControl & PowerAssist
Transfer switch
Maximum AC input current
DC Input voltage range
Output when in inverter mode
Cont. output power at 25 °C
(3)
Cont. output power at 25 °C
Cont. output power at 40 °C
Cont. output power at 65 °C
Maximum apparent feed-in power
Peak power
Maximum efficiency
Zero load power
Zero load power in AES mode
Zero load power in Search mode
Maximum output current
AC Input
Charge voltage 'absorption'
Charge voltage 'float'
Storage mode
Maximum battery charge current (4)
Battery temperature sensor
Auxiliary output
External AC current sensor (optional)
Programmable relay (
5)
Protection
(2)
VE.Bus communication port
General purpose com. port
Remote on-off
Operating temperature range
Humidity (non-condensing)
Material & Colour
Protection category
Battery-connection
120/240 VAC-connection
Weight
Dimensions (hxwxd) mm
Safety
Emission, Immunity
1) Can be adjusted to 50 Hz
2) Protection key:
a) output short circuit
b) overload
c) battery voltage too high
d) battery voltage too low
e) temperature too high
f) 120 VAC on inverter output
g) input voltage ripple too high
20
Yes
50 A
50 A
INVERTER
9,5 – 17 V
Output voltage: 120 VAC ± 2 %
Frequency
60 Hz ± 0,1 %
:
3000 VA
2400 W
2200 W
1700 W
2500 VA
5500 W
93 %
13 W
9 W
3 W
85 A peak, 70Arms for 1sec.
CHARGER
Split phase: 190-280 VAC 45 – 65 Hz
Single phase: 95-140 VAC 45 – 65 Hz
57,6 V
55,2 V
52,8 V
35 A
Yes
GENERAL
Yes (50 A)
100 A
Yes
a – g
For parallel and three phase operation,
remote monitoring and system integration
Yes, 2x
Yes
-40 to +65 °C (fan assisted cooling)
max 95 %
ENCLOSURE
Steel, blue RAL 5012
IP22
M8 bolts
Screw terminals 13 mm² (6 AWG)
19 kg
536 x 275 x 147
STANDARDS
EN-IEC 60335-1, EN-IEC 60335-2-29
EN 55014-1, EN 55014-2
EN-IEC 61000-3-2, EN-IEC 61000-3-3
IEC 61000-6-1, IEC 61000-6-2, IEC 61000-6-3
3) Non-linear load, crest factor 3:1
4) At 25 °C ambient
5) Programmable relay which can be set for general alarm, DC
under voltage or genset start/stop function. AC rating: 120 V/4 A,
DC rating: 4 A up to 35 VDC and 1A up to 60 VDC
(1)