6.2 Connecting Additional Grounding
DANGER
An external grounding point is provided at the upper left of the inverter. Prepare M5 OT
terminals, strip the grounding cable insulation, insert the stripped part of the grounding cable
into the ring terminal lug and crimp using a crimping tool. Additional grounding connection for
inverter:
PH2x150mm
2.5Nm
Position
1
2
3
4
© 2023 Maxeon Solar Technologies, Ltd. All rights reserved. | 547143 Revision B - June 2023
Specifications included in this document are subject to change without notice
Standard PV cable in the
industry
Standard network
cable in the industry
(recommended type:
C-Bus)
Electric Shock Hazard: Before doing electrical connection, please ensure
the PV switch & all AC and BAT circuit breakers in the energy storage
system are switched off and cannot be reactivated.
1
2
4
Designation
Housing
M5 terminal lug with protective conductor
M5x12 PH2 head screw
PE cable
16mm²