Maxeon SunPower Reserve Instrucciones De Instalación página 57

Sistema de almacenamiento de energía para el hogar
Ocultar thumbs Ver también para SunPower Reserve:

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

Error No. Error description Solution
100042
Output_short_
circuit
100043
Output_overload
100052
Backup_ovp
7
BMS lost
60002
Circuit_Breaker_
Open
60004
Slave_Battery_
Communication_
Lost
60006
Master_Battery_
Communication_
Lost
60008
Multi_Master_
error
5
Grid meter lost
6
PV meter lost
© 2023 Maxeon Solar Technologies, Ltd. All rights reserved. | 547143 Revision B - June 2023
Specifications included in this document are subject to change without notice
1.
Use a multimeter to test the impedance of the offgrid
output. If it is small, check whether the wiring is correct.
2. Restart the inverter to see if the fault still exists. Ifit still
exists, please call the service center.
Check whether the load exceeds the rated power. Restart the
inverter to see if the fault still exists. If it still exists, please call
the service center.
Restart the inverter to see if the fault still exists. If it still exists,
please call the service center.
BMS lost
1.
Check whether the BMS communication connection
between the battery and the inverter is normal.
2. Check if the battery is switched on
3. If the fault can't be cleared, please contact the service
center for further check. service center for further check.
Try to switch on all batteries breakers, If the action
cannot solve the problem, please contact customer
service.
Check the communication cables between batteries
Grid side meter lose
1.
Check whether the system configuration parameters are
correct and whether the meter is used on the grid side
2. Check whether the communication cable of the grid meter
is connected correctly (RS485: 3A6B).
3. Check whether the communication configuration
parameters of the grid meter is correct (communication
address and baud rate).
4. If the fault can't be cleared, please contact the service
center for further check.
PV inverter side meter lose
1. Check whether the system configuration parameters are
correct and whether the meter is used at the PV inverter
side
2. Check whether the communication configuration
parameters of the meter of PV inverter side is correct
(communication address and baud rate). (RS485: 3A6B).
3. Check whether the communication configuration
parameters of the meter of PV inverter side is correct
(communication address and baud rate).
4. If the fault can't be cleared, please contact the
customer service center for further check.