The table below shows how the HPP has been preprogrammed
These parameters should not be changed as they may cause the HPP to function incorrectly. If any of the settings
have been altered please refer to this list before contacting Dantherm.
Parameter checking.
Parameter list
Note
26
PARAMETER LIST
Press the SET button for 10 seconds to enter the parameter checking interface, then press M to enter the
parameter settings.
The parameters can be adjusted by pressing the
Pressing the set button saves the change and switches to other parameter settings.
When in the parameter checking mode press the
Parameters can be checked and adjusted when the HPP is in standby mode but parameters cannot be
changed when the HPP is running.
Any changes to the parameters will not be saved if the power supply fails within 10 seconds of any
adjustments.
No
Parameter name
0
Memory function if power off
1
Timer cycle
X (Temp difference between inlet water temp
2
and setting water temp to start compressor)
Y (Temp difference between inlet water temp
3
and setting water temp to stop compressor)
4
The interval for defrosting
5
Defrosting entry coil temperature
6
Defrosting off coil temperature
7
Defrosting max duration
8
Compressor exhaust gas protection
9
Setting temperature upper limit
10
Water pump running mode
Pump-off time after reaching setting water
11
temperature
12
Second anti-freezing mode
*13
See
Unit mode selection
Note
below
14
Inlet water temperature
15
Outlet water temperature
16
Coil temperature
17
Exhaust gas temperature
18
Ambient air temperature
* Changing the value of parameter 13 from 2 to 0 changes the running mode of the HPP from water
heating to water cooling.
The HPP is supplied as a pool water heater but is also able to cool the pool water.
The cooling mode is only recommended if ambient temperatures are likely to cause uncomfortably warm
pool water temperatures.
When the HPP is in water cooling mode the maximum temperature the water can be cooled to is 28°C
or
buttons.
or
button to exit parameter checking menu.
Range
0 (no) 1 (yes)
0 (once) 1 (every day)
2-10°C
0-3°
30-90mins
-30 - 0 (- and + are not
displayed)
2-30°C
0-15mins
90-120°C
40-65°C
0 (Special) 1 (Normal)
3-20mins
0 (heat pump)
1 (electric heater)
0 (cooling only)
1 (cooling and heating)
2 (heating only)
-0-99°C
-0-99°C
-0-99°C
-0-127°C
-0-99°C
Setting
1
1
3
0
40mins
-7 (Displayed as 7)
20
8mins
118°C
(Displayed as B8)
40
1
15
1
2
Actual temperature
Actual temperature
Actual temperature
Actual temperature
Actual temperature