C85A C120A LMV2x / 3x a control electrónico Quemadores de gas MANUAL DE INSTALACIÓN - USO - MANTENIMIENTO BURNERS - BRUCIATORI - BRULERS - BRENNER - QUEMADORES - ГОРЕЛКИ M039440FA Rel 0.3 11/2021...
Página 2
DANGERS, WARNINGS AND NOTES OF CAUTION THIS MANUAL IS SUPPLIED AS AN INTEGRAL AND ESSENTIAL PART OF THE PRODUCT AND MUST BE DELIVERED TO THE USER. INFORMATION INCLUDED IN THIS SECTION ARE DEDICATED BOTH TO THE USER AND TO PERSONNEL FOLLOWING PRODUCT INSTALLATION AND MAINTENANCE.
Página 3
3b) FIRING WITH GAS, LIGHT OIL OR OTHER FUELS DIRECTIVES AND STANDARDS Gas burners GENERAL European directives The burner shall be installed by qualified personnel and in compliance -Regulation 2016/426/UE (appliances burning gaseous fuels) with regulations and provisions in force; wrong installation can cause -2014/35/UE (Low Tension Directive) injuries to people and animals, or damage to property, for which the -2014/30/UE (Electromagnetic compatibility Directive)
Página 4
Burner data plate Type Gas - Light oil burners For the following information, please refer to Model Year European Directives the data plate: S.Number -Regulation 2016/426/UE (appliances burning gaseous fuels) burner type and burner model: must be Output Oil Flow -2014/35/UE (Low Tension Directive) reported in any communication with the Fuel...
Página 5
PARTE I: CARACTERÍSTICAS TÉCNICAS PARTE I: CARACTERÍSTICAS TÉCNICAS CARACTERÍSTICAS DE LOS QUEMADORES Quemador con caja aspiración de aire en aluminio Quemador con caja aspiración de aire en polímero (ABS) Nota: el dibujo es indicativo Panel sinóptico con interruptor de encendido Cuerpo de válvulas de gas Cuadro electrico Tapa...
Página 6
Identificación de los quemadores Los quemadores se identifican por tipo y modelo. Seguidamente se ilustran los modelos. Tipo C85A Modelo MD. SR. QUEMADOR TIPO C85A, C120A COMBUSTIBLE M - Gas natural B - Biogás L - LPG FUNCIONAMIENTO: (Versiones disponibles) PR - Progresivo MD - Modulante TOBERATIPO DE TOBERA Y CAJA ASPIRACIÓN...
Página 7
PARTE I: CARACTERÍSTICAS TÉCNICAS QUEMADOR TIPO C85A M-.. C120A M-.. C85A L-.. C120A L-.. 230 - 850 300 - 1200 230 - 850 300 - 1200 Potencialidad min. - max. kW Gas Natural G.P.L. Combustible Categoría ves párrafo siguiente 3B/P...
Página 8
Dimensiones (mm) C85A - C120A - Quemador con caja aspiración de aire en aluminio Plantilla de perforación recomendada de la placa de la caldera. (BS-BL) O min brida de quemador. O max (AS-AL) (AS) (AL) (BS) (BL) (**) C85A 1065 1155...
Página 9
1085 1195 1062 718 1036 692 (**) la cuota “V” concierne las dimensiones del filtro gas, cuando no comprendido en el grupo válvulas (VGD de DN65 en luego) B*: Las longitudes especiales de las boquillas se acordarán con la Cib Unigas...
Página 10
El quemador es idóneo solamente si el punto de intersección "A" de las dos rectas cae dentro del campo de trabajo.Los datos corre- sponden a condiciones estándares: presión atmosférica igual a 1013 mbar, temperatura ambiente igual a 15°C. Campos de aplicación C85A C120A C120A L- Para obtener la potencia en Kcal/h, multiplicar el valor en kW por 860.
Página 11
Curvas de presión - caudal en la red Quemadores de gas natural C85A M-.. C120A M-.. C120A L-.. ATENCIÓN! en abscisa es representado el valor del cudal gas, en entrada el correspondiente valor de presión en red a lo neto de la presión en cámara de combustión. Para conocer la presión mínima en entrada rampa, necesaria para conseguir el caudal gas solicitado, hace falta sumar la presión en cámara de combustión al valor...
Página 12
PARTE I: CARACTERÍSTICAS TÉCNICAS Curvas de presión en cabezal de combustión - caudal gas .Las curvas presión - caudal se refieren al quemador en combustión (porcentaje de O2 residual en los humos conforme a la tabla “Parámetros de combustión recomendados” y CO dentro de los límites establecido por las normas), con cabezal de combustión en su máxima apertura, servomando al máximo y mariposa del gas a la máxima apertura.
Página 13
PARTE I: CARACTERÍSTICAS TÉCNICAS Curvas de presión - caudal en cabezal de combustión ¡Las curvas se refieren a presión = 0 en la cámara de combustión! C85A M-.. C120A M-.. C120A L-.. Los valores de los diagramas se refieren a Gas Natural con un poder calorífico de 8125 kcal/Stm (15°C, 1013 mbar) y una...
Página 14
PARTE II: MANUAL DE INSTALACIÓN PARTE II: MANUAL DE INSTALACIÓN MONTAJE Y CONEXIÓNES ATENCIÓN: las operaciones señaladas a continuación las realiza (siempre y exclusivamente) personal especiali- zado conforme a las instrucciones del manual y de acuerdo con las normas de seguridad y salud en vigor. Las maniobras de transporte y/o manipulación solo deben iniciarse una vez que se haya comprobado la existencia de sistemas de traslado y elevación, dimensiones totales necesarias, distancias de seguridad, lugares aptos en tér- minos de espacio y de entorno para la colocación y medios adecuados para la operación.
Página 15
PARTE II: MANUAL DE INSTALACIÓN El quemador nace para funcionar situado según la figura indicada bajo. Por instalaciones diferentes, se ruega contactar el despacho técnico. ALTO Nota: el dibujo es indicativo BAJO Montaje del quemador a la caldera Para instalar el quemador en la caldera proceda de la siguiente manera: perforar la placa de cierre de la cámara de combustión como se describe en el párrafo ("Dimensiones ocupadas");...
Página 16
PARTE II: MANUAL DE INSTALACIÓN ATENCIÓN! Sellar el espacio entre la tobera y el material comprimido refractario, con material aislante (cordón de fibra resistente a la temperatura o cemento refractario. La longitud de las toberas no siempre cumple con este requisito, por lo cual podría ser necesario utilizar un distanciador de medida adecuada, que sirve para alejar el quemador en modo de conseguir la medida más arriba solicitada.
Página 17
PARTE II: MANUAL DE INSTALACIÓN ESQUEMA DE INSTALACIÓN RAMPA DE GAS En los diagramas indicados se muestran los esquemas con los componentes incluidos en el suministro y aquéllos que deberán ser montados por el instalador. Los esquemas detallan la exigencia de las vigentes normativas legales. Nota: el dibujo es indicativo flechas de “dirección”...
Página 18
PARTE II: MANUAL DE INSTALACIÓN Ensamblaje de la rampa del gas MultiBloc MB-DLE - red de distribución del gas Brida Filtro gas Cuerpo de válvulas de gas Juntura antivibrante MULTIBLOC DUNGS Montaje Montar la brida sobre la tuberías: utilizar oportunas guarniciones por gas MB-DLE 405..412 Insertar lo equipo MB-DLE y hacer particular caso a los O-ring MB-DLE 415..420...
Página 19
PARTE II: MANUAL DE INSTALACIÓN Control de la estanqueidad integrado (para quemadores equipados con LME7x, LMV, LDU) A continuación se describe el funcionamiento del control de estanqueidad integrado: Inicialmente ambas válvulas EV1, EV2 están cerradas Fase de evacuación: la válvula EV2 (lado del quemador) se abre y se mantiene en esta posición ...
Página 20
PARTE II: MANUAL DE INSTALACIÓN ESQUEMA DE LAS CONEXIONES ELÉCTRICAS ATENCIÓN: el quemador (versiones de dos llamas y progresivo) se suministra con un puente eléctrico entre los bornes 6 y 7; si debe ser conectado el termostato alta/baja llama, eliminar dicho puente antes de conectarlo. La seguridad eléctrica del equipo se obtiene cuando éste ha sido correctamente verificado por personal profe- sionalmente calificado ATENCION : Está...
Página 21
PARTE II: MANUAL DE INSTALACIÓN Nota su la alimentación eléctrica Si la alimentación eléctrica del quemador es de 230 V trifásica o 230 V fase-fase (sin neutro), con el equipo Siemens LME.. entre el borne 2 (borne X3-04-4 por LMV2x, LMV3x, LMV5x, LME7x) del soporte y el borne de tierra se deberá agregar el circuito RC Sie- mens, RC466890660.
Página 22
PARTE II: MANUAL DE INSTALACIÓN QUEMADORES CON VARIANTE INVERSOR (si se suministran) XXXXX M-. MD. xx. xx. x. x. xxx. EI. XXXXX M-. MD. xx. xx. x. x. xxx. EG. LMV5 DANFOSS XXXXX MG. MD. xx. xx. x. x. xxx. EK. XXXXX MG.
Página 23
PARTE II: MANUAL DE INSTALACIÓN QUEMADORES CON VARIANTE INVERSOR (si se suministran) KOSTAL Tipo Modello XXXXX M-. MD. xx. xx. x. x. xxx. EI. XXXXX M-. MD. xx. xx. x. x. xxx. EG. LMV5 XXXXX MG. MD. xx. xx. x. x. xxx. EK. XXXXX MG.
Página 24
PARTE III: FUNCIONAMIENTO PARTE III: FUNCIONAMIENTO PELIGRO : la rotación no correcta del motor es un peligro para las personas ATENCIÓN: antes de poner en funcionamiento el quemador, asegurarse de que las válvulas manuales de interceptación estén abiertas, y controlar que el valor de presión antes de la rampa sea conforme a los valores indicados en el apartado “Datos técnicos”.
Página 25
PARTE III: FUNCIONAMIENTO Fig. 1 Panel frontal cuadro eléctrico Leyenda Chivato de señalización bloqueo Chivato de señalización funcionamiento en llama alta Chivato de señalización funcionamiento en llama baja Chivato de señalización funcionamiento transformador de encendimiento Chivato de señalización intervención del relé térmico Motor ventilador . Chivato de señalización funcionamiento electroválvula EV2 Chivato de señalización funcionamiento electroválvula EV1 Chivato de señalización consenso presóstato gas...
Página 26
PARTE III: FUNCIONAMIENTO REGULACIÓN CAUDAL AIRE Y GAS PELIGRO! Durante las operaciones de calibración prestar atención para no hacer funcionar el quemador con caudal de aire insuficiente (peligro de formación de monóxido de carbono); si esto sucediera reducir lentamente el combustible hasta lograr los valores de combustión normales. ¡IMPORTANTE! el exceso de aire de combustión se debe regular según los parámetros recomendados, reprodu- cidos en la siguiente tabla: Parámetros de combustión recomendados...
Página 27
PARTE III: FUNCIONAMIENTO Botón F Para ajustar el accionamiento por combustible (Fuel): : Mantener pulsado el botón F y ajustar el valor mediante los botones + o -. Botón A Para ajustar el accionamiento por aire (Air): Mantener pulsado el botón A y ajustar el valor mediante los botones + o -. Botónes F + A Presionando al mismo tiempo los dos botones de la pantalla aparece escrito “code”...
Página 28
PARTE III: FUNCIONAMIENTO Mensaje de fallo Llama presente Se abre la válvula Se activa la ignición Se activa el motor ventiladorr Se activa precalentador aceite Modo de parametrización Modo informativo Modo de mantenimiento El actuador cierra El actuador abre Unidad de la indicación actua MENÚ...
Página 29
PARTE III: FUNCIONAMIENTO Primer tiempo de seguridad (transformador de encendido OFF) TSA1 = 1st safety time (ignition transformer OFF) Ph42 t42 = preignition time OFF Ph44 Intervalo 1 t44 = interval 1 Ph50 Segundo tiempo de seguridad TSA2 = 2nd safety time Ph52 Intervalo 2 t52 = interval 2...
Página 30
PARTE III: FUNCIONAMIENTO Nivel Info Para entrar en el nivel de INFO, proceda de la siguiente desde cualquier posición del menú, pulsar simultáneamente los botones + y - luego el programa pasará al inicio: en la pantalla se visualiza OFF Pulsar el botón enter (InFo)hasta que en la pantalla se visualiza InFo inmediatamente después en la pantalla se visualiza el primer código (167) parpadeante con el eventual dato mermorizado a la derecha.
Página 31
PARTE III: FUNCIONAMIENTO miento) Si durante el funcionamiento si visualiza un mensaje como: significa que el quemador está bloqueado (Lockout) con código de error (Error code): en el ejemplo “Código error: 4”. También se visualizará de forma alternada el mensaje “Código diagnóstico”...
Página 32
PARTE III: FUNCIONAMIENTO El nivel Service permite visualizar información sobre la intensidad de la llama, la posición de servomandos, el número y los códigos de bloqueo. Intensidad de la llama % potencia de salida, si fuera indefinido = funcionamiento automático ¡ATENCIÓN! : dejar el parámetro como se establece por defecto, de lo contrario el quemador no se vuelve a encender Posición servomandos, 00= fuel;...
Página 33
PARTE III: FUNCIONAMIENTO Quemadores modulantes Para regular los quemadores modulantes, utilizar el selector CMF presente en el panel de control del quemador (véase figura), en lugar de utilizar el termostato TAB como se describe en la regulación de los quemadores progresivos. Realizar la regulación como se describe en los apartados anteriores, prestando atención al uso del selector CMF.
Página 34
PARTE III: FUNCIONAMIENTO Regulaciones del grupo valvulas MB-DLE T(VR) El Multibloc es un grupo compacto compuesto por dos válvulas, presostato gas, estabili- zador de presión y filtro gas. Puede ser combinado con los controles de estanqueidad Dungs VPS504. La regulación de la válvula gas se realiza mediante el regulador RP, tras haber aflojado de algunas vueltas el tornillo de bloqueo VB.
Página 35
PARTE III: FUNCIONAMIENTO MultiBloc MBE Regulación VD-R con PS No lineal! Se pueden conectar varios sensores.Presión de salida según el rango de medición del sensor. Aumentar la presion Ajuste de la presión de salida según el fabricante de la calefacción. Reducir la presion Al ajustar la presión de salida, no se deben alcanzar ni exceder las condiciones de operación de peligro.
Página 36
PARTE III: FUNCIONAMIENTO Calibración de los presostatos de aire y de gas El presostato de aire cumple la función de poner en condiciones seguras (bloquear) el equipo de control de la llama si la presión del aire no es la prevista. En caso de bloqueo, desbloquear el quemador sirviéndose del botón de desbloqueo del equipo, presente en el panel de control del quemador.
Página 37
PARTE IV: MANTENIMIENTO PARTE IV: MANTENIMIENTO Al menos una vez al año realizar las operaciones de mantenimiento indicadas seguidamente. Si el servicio de mantenimiento se realiza en cada estación, es aconsejable efectuarlo a fines de cada invierno; si el servicio es de tipo continuativo, mantenimiento debe ser realizado cada 6 meses.
Página 38
PARTE IV: MANTENIMIENTO Extracción del filtro en el grupo MB-DLE MB-DLE 415 - 420 B01 405..412 0 CoperFKLR GHO ¿OWro 1,3,4,6 TDSSR D YLWH * 2 AWWDFFR PLVXrDWRre 5 TDSSR D YLWH 0 0, 1, 2, 3, 4, 5 7DSSR D YLWH * Prese di pressione Prese di pressione...
Página 39
PARTE IV: MANTENIMIENTO Mantenimiento del filtro de gas Para limpiar o sustituir el filtro de gas proceder de la siguiente manera: quitar la tapa desenroscando los tornillos de bloqueo (A); desmontar el cartucho filtrante (B), limpiarlo con agua y jabón, aplicar aire comprimido (o sustituirlo si fuera necesario) 3 volver a montar el cartucho en su posición inicial, controlando que se encuentre entre las guías apropiadas y que no obstaculice el montaje...
Página 40
PARTE IV: MANTENIMIENTO Sustitución de los electrodos ATENCIÓN: para no afectar el funcionamiento del quemador, evitar el con- tacto de los electrodos de encendido y detección con partes metálicas (cabeza, boca, etc.) Controlar la posición de los electrodos después de cada intervención de mantenimiento en la cabeza de combustión.
Página 41
PARTE IV: MANTENIMIENTO Control de la corriente de detección con electrodo (Gas natural) Para medir la señal de detección, seguir el esquema indicado en figura. Si la señal es inferior al valor indicado, controlar la posición del electrodo o célula fotoeléctrica de detección, los contactos eléctricos y, eventualmente, sustituir el electrodo de detección o célula foto- eléctrica.
Página 42
PARTE IV: MANTENIMIENTO TABLA DESCRIPCIÓN DE PROBLEMAS - CAUSAS - SOLUCIONES Funcionamiento del gas * No hay suministro de energía * Ripristine l’alimentazione * Interruptor principal abierto * Cerrar el interruptor * Termostatos abiertos * Revisar los puntos de ajuste y las conexiones de los termostatos * Mal punto de ajuste o termostato roto * Resetear o reemplazar el termostato * Falta de presión de gas...
Página 44
C.I.B. UNIGAS S.p.A. Via L.Galvani, 9 - 35011 Campodarsego (PD) - ITALY Tel. +39 049 9200944 - Fax +39 049 9200945/9201269 web site: www.cibunigas.it - e-mail: cibunigas@cibunigas.it Los datos contenidos en este catálogo son solamente indicativos pues no tienen carácter vinculante; la empresa se...
Página 45
AZL2x - LMV2x/3x Control electronico de quemador con regulación integrada de proporción combusible/aire Manual uso y taratura instrumento 03/2023 M12916FD Rev. 3.4...
Página 46
INDICE ADVERTENCIA ....................................3 CARACTERÍSTICAS GENERALES ............................... 6 Interfaz de usuario ..................................6 Estructura de los niveles de parametrización ..........................8 MENÚ DE CONFIGURACIÓN................................ 9 Parámetros 000: Parámetros internos ............................10 Parámetros 100: General................................10 Parámetros 200: Unidad básica..............................13 Parámetros 400: Curvas de proporción ............................
Página 47
ADVERTENCIA EL MANUAL DE INSTALACIÓN, USO Y MANTENIMIENTO FORMA PARTE INTEGRANTE Y ESENCIAL DEL PRODUCTO Y COMO TAL DEBE SER SUMINISTRADO AL USUARIO. LAS ADVERTENCIAS CONTENIDAS EN ESTE CAPÍTULO ESTÁN DIRIGIDAS TANTO AL USUARIO COMO AL PERSONAL QUE DEBERÁ REALIZAR LA INSTALACIÓN Y EL MANTENIMIENTO DEL PRODUCTO. EL USUARIO ENCONTRARÁ...
Página 48
no tirar de los cables eléctricos. DIRECTIVAS Y NORMAS APLICADAS no dejar el equipo expuesto a condiciones atmosféricas (lluvia, sol, etc.) a menos que no esté explícitamente previsto. Quemadores de gas Directivas europeas: no permitir que el equipo sea utilizado ni por niños ni por personas - 2009/142/CE (Directiva gas);...
Página 49
- UNI EN 676 (Quemadores de gas); Este símbolo indica las instrucciones - UNI EN 267 quemadores de mono - blo- queo de aceite combustible y que, en caso de no ser tenidas en cuenta, pueden acarrear graves con- con pulve- rización PELIGRO! secuencias tanto físicas como mate- - EN 55014-1 Compatibilidad electromagnética, requisitos para aparatos...
Página 50
CARACTERÍSTICAS GENERALES El sistema de control electrónico se compone de la unidad central Siemens LMV que integra todas las funciones de control del quemador y de la unidad local de programación Siemens AZL que actúa como interfaz del usuario. Leyenda Quemador AZL2..
Página 51
Botón F Para ajustar el accionamiento por combustible (Fuel): : Mantener pulsado el botón F y ajustar el valor mediante los botones + o -. Botón A Para ajustar el accionamiento por aire (Air): Mantener pulsado el botón A y ajustar el valor mediante los botones + o -. Botónes F + A Presionando al mismo tiempo los dos botones de la pantalla aparece escrito “code”...
Página 52
Estructura de los niveles de parametrización...
Página 53
MENÚ DE CONFIGURACIÓN El menú de configuración se divide en diferentes bloques de parámetros: Description Parámetros internos Internal parameters OEM / Service Información General General OEM / Service / Info Unidad básica Burner control OEM / Service Unidad básica (LMV26) Burner control (LMV26 only) OEM / Service Curvas de proporción...
Página 54
Parámetros 000: Parámetros internos Parámetro Description Nivel de coantraseña Contraseña HF (4 caracteres) Password heating engineer (4 characters) Contraseña OEM (5 caracteres) Password OEM (5 characters) Iniciar el respaldo / la restauración mediante AZL2... / herramienta de PC (parametrizar a Start backup / restore via AZL2.../ PC sof- tware (set parameter to 1) Index 0: Create Índice 0 = crear respaldo...
Página 55
Frecuencia de red Mains frequency 0 = 50 Hz 0 = 50 Hz Service / Info 1 = 60 Hz 1 = 60 Hz Luminosidad del display Display brightness Service / Info Expiración del tiempo de espera para el Timeout for menu operation (default value = manejo del menú...
Página 56
Especificación de potencia en caso de inter- rupción de la comunicación con la automati- zación de edificios Valores de ajuste: En el funcionamiento modulante, el rango de Performance standard at interruption of com- ajuste es: munication with building automation For 0…19,9 = quemador apagado modulation operation the setting range is as 20…100 = 20…100 % potencia del quema-...
Página 57
Parámetros 200: Unidad básica Parámetro Description Burner operating mode (fuel train, modula- ting / multistage, actuators, etc..) __= undefined (delete curves) 1 = gas direct ignition (G mod) 2 = ignition by gas pilot connected between Modo de funcionamiento del quemador (canal the two gas solenoid valves EV1/EV2 (Gp1 de combustible modulante / multietapa, accio- mod)
Página 58
15 =Gp1 mod pneu sin accionamiento 15 = Gp1 mod pneu without actuator 16 =Gp2 mod pneu sin accionamiento 16 = Gp2 mod pneu without actuator 17 =Lo 2 etapas sin accionamiento 17 = Lo 2-stage without actuator 18 =Lo 3 etapas sin accionamiento 18 = Lo 3-stage without actuator 19 =G mod sólo accionamiento por gas 19 = G mod gas actuator only...
Página 59
Gas: active detector flame evaluation (default Gas: Sensor activo de la evaluación de llama value = 1) 0 = QRB../QRC.. OEM / Service 0 = QRB../QRC.. 1 = ION / QRA.. 1 = ION / QRA.. Gas: Pre-purging (default value = 1) Gas: Preventilación 1 = active 0 = inactivo...
Página 60
Gas: Entrada de presostato-mín. Gas: Pressure switch-min input 0 = inactivo 0 = inactive 1 = Presostato-mín. (antes de la válvula de 1 = pressure switch-min (upstream of fuel combustible 1 (V1)) OEM / Service valve 1 (V1)) 2 = Control de estanqueidad mediante preso- 2 = valve proving via pressure switch-min stato-mín.
Página 61
Gas: Control de estanqueidad tiempo de lle- Gas: proving test filling time (default value = nado (Ajuste básico: 3s. Rango de valores: 3s - range:0.2s - 10s) 0.2s - 10s) Gas: Control de estanqueidad tiempo de Gas: proving test time gas pressure (default prueba de presión de gas (Ajuste básico: 10s.
Página 62
Aceite: Intervalo 1 (Ajuste básico: 2s- Rango Oil: Interval 1 (default value = 2s - OEM / Service de valores: 0.2s - 60min) range:0.2s - 60min) Aceite: Tiempo de seguridad 2 (TSA2) (Aju- Oil: safety time 2 (TSA2) (default value = 3s ste básico: 3s.
Página 63
Parámetros 300: Unidad básica (solamente LMV26) Parámetro Description Combustible 1: Modo de funcionamiento del Fuel 1 : Burner operating mode (fuel train, quemador (rampa combustible, modulante / modulating / multistage, actuators, etc..) multietapas, servomandos, etc.) __=no determinado (borrado curvas) __= undefined (delete curves) 1 =encendido directo con gas (G mod) 1 = gas direct ignition (G mod) 2 =encendido mediante piloto gas con cone-...
Página 64
17 =Lo 2 etapas sin accionamiento 17 = Lo 2-stage without actuator 18 =Lo 3 etapas sin accionamiento 18 = Lo 3-stage without actuator 19 =G mod sólo accionamiento por gas 19 = G mod gas actuator only 20 =Gp1 mod sólo accionamiento por gas 20 = Gp1 mod gas actuator only 21 =Gp2 mod sólo accionamiento por gas 21 = Gp2 mod gas actuator only...
Página 65
Combustible 1 gas: Intervalo 1 (Ajuste básico: Fuel 1 - Gas: Interval 1 (default value = 2s - OEM / Service 2s.Rango de valores: 0.2s - 60min) range: 0.2s - 60min) Combustible 1 gas: Tiempo de seguridad 2 Fuel 1 - Gas: Safety time 2 (TSA2) (default (TSA2) (Ajuste básico: 3s.Rango de valores: value = 3s - range:0.2 - 10s) 0.2 - 10s)
Página 66
Combustible 1 gas: Ejecución del control de Fuel 1 - Gas: execution proving test (default estanqueidad value= 2) 0 =sin control de estanqueidad 1 =control de estanqueidad durante la puesta 0 = no proving test en marcha 1 = proving test on startup OEM / Service 2 =control de estanqueidad durante la puesta 2 = proving test on shutdown...
Página 67
Fuel 1 - Oil: prepurging (default value = 1) 0 = deactivated Combustible 1 aceite: Preventilación 1 = activated 1 =activo 0 = deactivated 0 =inactivo OEM / Service WARNING: in the civil field, the prepurge is mandatory according to the standard EN267. In the industrial fiels, check if the pre purge can be avoided according to the standard EN746-2...
Página 68
Valor de limitación de repetición pérdida de Repetition limit value loss of flame (default llama value = 2 - range:1 - 2) 1 = Sin repetición 2 = 1 repetición (Ajuste básico: 2. Rango de valores: 1-2) Combustible 1 aceite: Momento de ignición Fuel 1 - Oil: time oil ignition (default value = de aceite 0 =preencendido corto (fase 38)
Página 69
Parámetros 400: Curvas de proporción Parámetro Description Curvas control servomando combustible (F): se accede a la lista de los puntos por con- Ratio control curve fuel actuator (F): it acces- figurar (de P0 a P9) - consultar el apartado ses to the parameter list of the points to be set OEM / Service “Configuración (P0 to P9) - see paragrapf “Setting the curves”...
Página 70
Parámetros 500: Proporción Parámetro Description No-flame position fuel actuator Posiciones sin llama accionamiento por com- bustible Índice 0 = posición de reposo = 0 Index 0 = no-load position = 0° OEM / Service Índice 1 = posición de preventilación = 0 Index 1 = prepurge position = 0°...
Página 71
Acelerar rampa Ramp up OEM / Service Desacelerar rampa Ramp down OEM / Service Activación del convertidor de frecuencia / ventilador PWM Activation of VSD / PWM fan OEM / Service 0=inactivo (PWM = Pulse-Width Modulation) 1=activo Parámetro 544 Modulación Modulación Modulación Modulación...
Página 72
Parámetros 600: Actuadores Parámetro Description Selección del punto de referencia Selection of reference point Índice 0 = combustible Index 0 = fuel Índice 1 = aire Index 1 = air 0 = Cerrado (<0°) 0 = closed (<0°) 1 = Abierto (>90°) 1 = open (>90°) Dirección de rotación del actuador Actuator’s direction of rotation...
Página 73
Type of referencing Tipo de referenciación Index 0 = fuel Índice 0 = combustible Índice 1 = aire Index 1 = air 3 = ambos 0 = standard 0 = estándar 1 = stop within usable range 1 = tope en el rango útil 2 = internal stop (SQN1...) 2 = tope interno (SQN1...) 3 = both...
Página 74
Atención: para el servomotor SQM3x imponer la rotación en base a la función del servomotor. Para el modelo de servomotor SQN1x, imponer siempre el sentido antihorario, independientemente del modelo seleccio- nado para el funcionamiento...
Página 75
Parámetros 700: Historial de fallos Description Historial de fallos: 701-725.01.Código Error history: 701 - 725.01.code Service / Info Historial de fallos: 701-725.02.Código de dia- Error history: 701 - 725.02.diagnostic code ° Service / Info gnóstico Historial de fallos: 701-725.03.Clase de fallo Error history: 701 - 725.03.error class °...
Página 76
Parámetros 900: Datos del proceso Description Potencia actual Current output (default value = 0% - range = 0-100%) Índice 0 = combustible Service / Info Index 0 = fuel Índice 1 = aire Index 1 = air Posición de paso de los actuadores Incremental position of actuators (default value = 0% - range = -50% - 150%) Índice 0 = combustible...
Página 77
Referenciación En el caso de la indicación de la posición, se trata de un codificador incremental. En consecuencia, tras el encendido se debe llevar a cabo una referenciación de los accionamientos. Además, al final de cada puesta fuera de servicio en la fase 10 se referencian los accionamientos, a fin de evitar que los errores de paso individuales se acumulen y conduzcan a una parada.
Página 78
PROGRAMACIÓN DE LA UNIDAD LMV La programación completa de la LMV solo debe de realizarse si el regulador nunca ha sido programado con anterioridad o si se ha sustituido (ejemplo repuesto) iSi la LMV es un repuesto introducir la identificación del quemador (parámetro “113”) al menos 4 cifras. Ajuste el tipo de rampa de combustible (parámetro “201”) Ajuste los puntos de la curva relación aire/combustible (grupo de parámetros “400”) Ajuste el porcentaje de potencia máxima (parámetro “546”)
Página 79
Description Modo de funcionamiento del quemador (rampa combustible, modulante / multietapas, servomandos, etc.) Burner operating mode (fuel train, mod / multi- __=no determinado (borrado curvas) stage, actuators, etc.) 1 =encendido directo con gas (G mod) __= undefined (delete curves) 2 =encendido mediante piloto gas con cone- 1 = gas direct ignition(G mod) xión entre las dos electroválvulas EV1/EV2 del gas (Gp1 mod)
Página 80
Lo 2-stage Lo 3-stage Si desea configurar, por ejemplo, la rampa de gas Gmod (Configuración 1). Selececiona el tipo de rampa pulsando ENTER y “+” pulsar ENTER para confirmer: se verá la cifra “1” a la derecha de la pantalla. Luego ajuste, presione ESC para salir, En este punto se ve Pulse la tecla “+”...
Página 81
Proceder de la misma manera descrita anteriormente para establecer los valores de abertura del servo de aire (A) y combustible (F) y eventualmente el invertir (F+A) en caso de poner la LMV37 Atención: Durante la primera calibración del qeumador, es aconsejable establecer el punto de máxima potencia al mismo valor que el punto de encendido (o ligeramente superior), con el fi de lograr trabajar en el punto P9 de una forma segura (Véase el párrafo siguiente) Pulsando la tecla “+”...
Página 82
Configuración "en caliente" Una vez pulsado el botón “enter”, si la serie termostática estuviera abierta, se visualizará el mensaje PH12, a continuación, cerrar la serie termostática y la unidad realiza todo el ciclo de preventilación (véase la tabla de fases) y se detienen en la posición P0 pero sin encenderse.
Página 83
dos hasta visualizar “Calc”: la unidad recalcula automáticamente la curva; 10 Automáticamente la unidad pasará al punto P8 calculado: comprobar la combustión en el punto, si fuera necesario modificarlo. 11 Pulsar el botón “-” para bajar a todos los puntos inferiores y comprobar la combustión, si fuera necesario modificar los puntos. Nota: si un punto intermedio (por ejemplo P5), la variación de la posición de los servomandos con respecto al punto P5 cal- culado desde la unidad es amplia, mantener pulsado el botón “-”...
Página 84
UPr. hasta que se configuren todos los puntos. Nota 4: si durante la parametrización de la curva, se produce un error que causa el bloqueo de seguridad, dicha parametriza- ción se interrumpirá.. Configuración "en frío" La configuración “en frío” (sin llama) se puede aplicar solo en el caso en que ya se conozcan los valores de los puntos de la curva (por ejemplo, en caso de sustitución de la LMV).
Página 85
ENCENDIDO DEL QUEMADOR CON LMV... YA PROGRAMADA Durante el encendido de la LMV, la pantalla de la AZL visualizará: El quemador sale de la fábrica con una programación básica. La curva de relación aire/combustible es configurada con el punto de potencia máxima P9 apenas por encima o igual a P0.
Página 86
Configurar la curva de relación aire/combustible como se describe en la sección "configuración en caliente" en el capítulo anterior "Pro- gramación de la LMV2x". Nota: otras fases son: Ph60 = funcionamiento (OP= en modulación) Ph62 = hacia el mínimo para el apagado Ph70 = apagado pero en ventilación después del burntime Ph72 = hacia la posición de postventilación Ph74 = postventilación (se visualizan los segundos de la cuenta regresiva)
Página 87
Enclavamiento manual El sistema se puede bloquear manualmente pulsando al mismo tiempo ENTER (InFo) y cualquier otro botón en la AZL2.. Esta función permite al usuario parar el sistema cuando se produce una emergencia. Para ejecutar el reset, se realizarán las siguientes operacio- nes: relé...
Página 88
Acceso a los niveles El acceso a los distintos niveles de los parámetros se puede hacer con las combinaciones adecuadas de los botones como se muestra en el siguiente diagrama de bloques: El quemador, y en consecuencia la LMV..., salen de la fábrica con una primera configuración y calibración de las curvas de aire y com- bustible.
Página 89
Nivel Info Para entrar al nivel Info proceder de la siguiente manera: desde cualquier posición del menú, pulsar simultáneamente los botones + y - luego el programa pasará al inicio: en la pantalla se visualiza OFF. Pulsar el botón enter (InFo)hasta que en la pantalla se visualiza InFo, inmediatamente después en la pantalla se visualiza el primer código (167) parpadeante con el eventual dato mermorizado a la derecha.
Página 90
miento) Si durante el funcionamiento si visualiza un mensaje como: significa que el quemador está bloqueado (Lockout) con código de error (Error code): en el ejemplo “Código error: 4”. También se visualizará de forma alternada el mensaje “Código diagnóstico” (Diagnostic code): en el ejemplo “Código diagnóstico: 3”. Registrar los números y comprobar en la tabla errores los tipos de avería.“...
Página 91
Nivel Service Para acceder al modo Service pulsar el botón InFo hasta que se visualice. El nivel Service permite visualizar información sobre la intensidad de la llama, la posición de servomandos, el número y los códigos de bloqueo. Intensidad de la llama % potencia de salida, si fuera indefinido = funcionamiento automático ¡ATENCIÓN! : dejar el parámetro como se establece por defecto, de lo contrario el quemador no se vuelve a encender...
Página 92
LISTA DE INDICACIONES DE FASE Durante el funcionamiento se visualizarán de manera sucesiva las diferentes fases del programa. En la siguiente tabla se reproduce el significado de cada fase. Fase /Phase Función Function Ph00 Fase de avería Lockout phase Ph01 Fase de seguridad Safety phase Ph10...
Página 93
RESPALDO PARÀMETROS MEDIANTE AZL2x En la AZL2x se puede guardar la configuración LMV para luego descargarla en otro equipo.. Para ello:: acceder a la programación pulsando simultáneamente F y A, se visualizará: introducir la contraseña según el procedimiento indicado en el capítulo “Programación de la LMV...”. Pulsar ENTER hasta que se visualice: con el botón pasar al grupo parámetros 000 y pulsar...
Página 94
RESTAURAR PARÀMETROS DE AZL2x A LMV.. Para copiar la configuración guardada previamente en AZL2x, proceder de la siguiente manera: acceder a la programación pulsando simultáneamente F y A, se visualizará: introducir la contraseña según el procedimiento indicado en el capítulo “Programación de la LMV...”. Pulsar ENTER hasta que se visualice: Para poder copiar la configuración de AZL2x a LMV..
Página 95
LISTA DE CÓDIGOS DE FALLO Código de Código de diagnóstico Significado para el sistema LMVx… Medidas recomendadas fallo No existe comunicación entre la unidad básica Comprobar si existe interrupción o contacto flojo del cableado no Comm LMV36… y la AZL2... Sin llama al final del tiempo de seguridad (TSA) Sin llama al final del tiempo de seguridad 1 (TSA1) Sin llama al final del tiempo de seguridad 2 (TSA2)
Página 96
Control de estanqueidad activado, pero no se ha asignado ninguna entrada (verificar los parámetros No es posible el control de estanqueidad 236 y 237) Control de estanqueidad activado, pero se han asignado dos entradas (ajustar el parámetros 237 a No es posible el control de estanqueidad presostato-máx.
Página 97
Cadena de seguridad / brida del quemador, luz externa, presión de combustión, POC - prevención de arranque Cadena de seguridad / brida del quemador, presión del aire, presión de combustión, POC - prevención de arranque Cadena de seguridad / brida del quemador, luz externa, presión del aire, presión de combustión, POC - prevención de arranque Rearmar, en caso de repetición del fallo sustituir el aparato...
Página 98
Fallo interno proporción: comprobación de sincronización de datos Potencia actual distinta Potencia deseada distinta Posiciones deseadas distintas Con el convertidor de frecuencia activado, puede ser causado por números de revoluciones de Se han alcanzado posiciones distintas estandarización distintos (por ej. tras la restauración del conjunto de datos). ...
Página 99
El motor no ha alcanzado un número de revoluciones estable tras la aceleración 1. Los tiempos de rampa del convertidor de frecuencia no se han ajustado más cortos que las rampas en la unidad básica (parámetros: 522, 523) 2. La curva característica del convertidor de frecuencia no es lineal. La configuración de la Fluctuación del número de revoluciones / tiempo de entrada de tensión en el convertidor de frecuencia debe coincidir con la de la unidad básica aceleración del convertidor de frecuencia demasiado...
Página 100
No se alcanzó el número de revoluciones, porque se activó la limitación del campo de regulación Bit 1 Limitación superior del campo de regulación de la Valor 2..3 regulación Para las medidas a adoptar, véase el código de fallo 80 No se alcanzó...
Página 101
Fallo de referenciación del accionamiento por aire No pudo completarse con éxito la referenciación del accionamiento por aire. No pudo alcanzarse el punto de referencia. 1. Verificar el ajuste del tipo de accionamiento (parámetros 613.1) 2. Comprobar si los accionamientos están invertidos 3. Comprobar si el accionamiento está...
Página 102
Medir los contactos: 3 Transformador de encendido 1. Unidad conectada a tensión: no debe existir tensión en la salida del ventilador 4 Válvula de combustible 1 2. Desconectar la tensión: retirar el ventilador. No debe existir conexión óhmica entre la salida del Relé...
Página 103
Fallo interno de la comprobación del monitor de Rearmar, en caso de repetición del fallo sustituir el aparato tensión Tensión de red demasiado baja Subtensión de red Factor de conversión código de diagnóstico valor de tensión (120 V: 0,843) Restablecimiento de la tensión de red Código de fallo para desencadenar un reset al restablecerse la tensión de red (no hay fallo) Rearmar, en caso de repetición del fallo sustituir el aparato...
Página 104
244 (-12) Los datos de respaldo son incompatibles Datos de respaldo incompatibles con la versión de software actual, no es posible la restauración 245 (-11) Fallo de acceso a Parameter Restore_Complete Rearmar y repetir la restauración Restauración – tiempo de espera expirado durante el 246 (-10) Rearmar y repetir la restauración guardado en EPROM...
Página 105
No hay fallo Sistema libre de fallos Prevención de arranque en caso de aparato no parametrizado UPr0 y En caso de apagado dentro del primer ajuste de curva, es preciso determinar la causa original del Prevención de arranque fallo mediante el historial de fallos, entrada 702. UPr1 Bit 0 No hay ningún modo de funcionamiento seleccionado...
Página 106
ESQUEMA DE CONEXIONES ELÉCTRICAS Conexiones eléctricas para LMV20 Alimentación eléctrica Brida quemador Mando del motor del ventilador Cadena de dispositivos de seguri- Señalización bloqueo Mando ventilador continuo Válvula V2 Válvula exteriorSV Transformador de encendido Válvula V1 Señalización funcionamiento Reset Reservas Común Aumentar potencia Presostato gas control de pérdi-...
Página 112
C.I.B. UNIGAS S.p.A. Via L.Galvani, 9 - 35011 Campodarsego (PD) - ITALY Tel. +39 049 9200944 - Fax +39 049 9200945/9201269 web site: www.cibunigas.it - e-mail: cibunigas@cibunigas.it La información contenida en este documento es puramente indicativa y no vinculante. La compañía se reserva el derecho a hacer cambios sin previo aviso.