Descargar Imprimir esta página

Mitsubishi Electric TRANE TCMBG-SJ11N4 Manual De Instalación página 7

Publicidad

Idiomas disponibles

Idiomas disponibles

Piping length and height between indoor unit and BC controller
100 [328]
90 [295]
80 [262]
70 [229]
60 [196]
50 [164]
40 [131]
30 [98]
20 [65]
10 [32]
0
Height difference between
the main BC controller and indoor unit (m) [ft]
Fig.1
BC
Fig.2
Fig.1
Indoor
unit
5 [16]
10 [32]
15 [49]
Fig.2
Sub
Sub
BC
BC
Fig.1
Fig.1
Indoor
Indoor
unit
unit
100 [328]
90 [295]
80 [262]
70 [229]
*3
60 [196]
50 [164]
40 [131]
30 [98]
20 [65]
10 [32]
0
5 [16]
Height difference between
the main BC controller and indoor unit (m) [ft]
Fig.2
*3 When the piping length or the height difference exceeds the restriction
specified in Fig. 1, connect a sub BC controller to the system. The
restriction for a system with a sub BC controller is shown in Fig. 2.
When a given system configuration falls within the shaded area in Fig. 2,
increase the size of the high-pressure pipe and the liquid pipe between
the main and sub BC controller by one size. When using P12, P15,
P18, P36, or P48 model of indoor units, increase the size of the liquid
branch pipe between the sub BC controller and indoor unit by one size.
When using P54 or larger model of indoor units, the restriction shown
in Fig. 1 cannot be exceeded.
10 [32]
15 [49]
7

Publicidad

loading

Este manual también es adecuado para:

Trane tcmbm-ja11n4Trane tcmbm-ka11n4Trane tcmbs-kb11n4