Step
Action
8
Reinstall the fuse and carrier in reverse order.
Reconnect the connection cable of the control system
9
to the kiln.
10
Turn on the kiln.
11
Turn on the control unit.
12
Check the control system works.
10. Parameter configuration
10.1.
General description
By changing the available parameters, the controller can be adapted to your individual requirements.
10.2.
Available parameters
Parameter
Function
Number
14
Kiln output in kW
Logging interval data
50
on USB in s
Temperature display in
60
°C or °F
Min.
Max.
value
Value
0
9999
5
300
0
1
79 / 293 - EN -
Remark
Tool:
7 mm slotted screwdriver
Set the main switch on the kiln to the
"I/ON" position and/or plug in the power
plug.
If the control unit still cannot be switched
on, contact a qualified electrician, the local
specialist or the manufacturer.
Default
Description of the value
setting
1 unit = 0.1 kW
E.g.:
0
For a kiln with 10 kW power
(see kiln nameplate), enter the
value "100" here.
60
1 unit = 1 s (second)
0 =°C
0
1 = °F