Indication on the
Meaning
display
0 % / 0 bar
This message appears when null balancing has failed.
Select "Yes" or "No" on the display.
Cancel null
balancing?
YES: The "VG" primary tank is empty and the device is
installed as per the instructions. If null balancing is
No
still not possible, cancel with "Yes". Contact your
Reflex Customer Service.
NO: Check the prerequisites for the commissioning,
 8.1 "Checking the requirements for
commissioning",  39.
Confirm the selection of "yes" or "no" with "OK".
Min.op.pressure
Enter the value for the minimum operating pressure.
01.8 bar
Note!
Calculation of minimum operating pressure,  8.2
"Variomat switching points",  39.
Switch to the "Degassing" sub-menu.
Degassing˃
Press "OK" to open the menu.
Use the "▼▲" buttons to open the next sub-menu.
Degassing
Switch to the next list item.
Degassing
Select between the degassing programmes:
programme
Continuous degassing
Interval
Interval degassing
degassing
For a detailed description,  9.1.1 "Automatic mode",
 42.
Time
Time setting for Continuous degassing.
Continuous.
The standard values during commissioning can be between
degas.
12 and 100 hours. The default setting is 12 hours.
12 h
Less times for continuous degassing are sufficient when
the following conditions apply:
Significant gauge pressure (≥ 0.5 bar above
atmospheric pressure) at the high point.
Little difference between the maximum temperature
at the high point and the degassing temperature.
Small system volume with low initial gas content due
to good initial ventilation, for example.
Make-up
Switch to the "Make-up" sub-menu.
Press "OK" to open the menu.
Use the "▼▲" buttons to open the sub-menu.
If the water content is below the specified tank size, add
water,  8.3 "Modifying the controller's start routine",
 39.
If an automatic make-up device (Fillcontrol for
example) is installed, make-up will be actuated
automatically; otherwise the make-up must be
manually activated.
Terminate the water make-up when the specified tank size
is exceeded.
If an automatic make-up device is installed, make-up
will be shut off automatically; otherwise the make-up
must be manually deactivated.
If you have selected "No" for automatic make-up, the
system will not return any further queries about the
make-up.
Max. make-up
Pre-selected time for a make-up cycle. Upon expiry of this
time
set time, the system interrupts the make-up and returns
the "Make-up time" fault message.
010 min.
Max. make-up
If the set number of make-up cycles is exceeded within two
cycles
hours, the system interrupts the make-up and returns the
"Make-up cycles" fault message.
003 / 2 h
With water
YES: FQIRA+ contact water meter is installed,  4.6
meter.
"Optional equipment and accessories",  29.
This is the prerequisite for the make-up quantity
YES
monitoring and the operation of a softening system.
NO: A contact water meter is not installed (standard
model).
Indication on the
display
Make-up
quantity
000020 l
Max. make-up
quantity
000100 l
With softening
YES
Disable make-
up?
YES
Hardness
reduction
10 °dH
Cap. soft water
05000 l
Remaining cap.
soft w.
000020 l
Replacement
18 months
Next
maintenance
012 months
Floating fault
contact
YES
Fault memory˃
ER 01...xx
Parameter
memory˃
Variomat Basic — 09.09.2022-Rev. C
Meaning
Only displayed if "YES" has been set in the "With water
meter" menu option.
Use "OK" to delete the counter.
Press "YES" to reset the value displayed to "0".
Press "NO" to retain the displayed value.
This value is only displayed if "YES" has been set in the
"With water meter" menu option.
When the set quantity is exceeded, the system
interrupts the make-up process and returns the error
message "Max. make-up quantity exceeded".
This value is only displayed if "YES" has been set in the
"With water meter" menu option.
YES: Further queries follow about softening.
NEIN: The system does not offer more queries
regarding the softening process.
This value is only displayed if "YES" has been set in the
"With softening" menu option.
YES: The system stops the make-up process when the
set soft water capacity is exceeded.
NEIN: The system does not stop the make-up process.
The system displays the "Softening" message.
This value is only displayed if "YES" has been set in the
"With softening" menu option.
Hardness reduction is calculated from the difference
of the overall water hardness GH
water hardness GH
.
target
Hardness reduction = GH
actual
Enter the value in the controller. Consult the manufacturer
information for third-party products.
This value is only displayed if "YES" has been set in the
"With softening" menu option.
The attainable soft water capacity is calculated from the
type of softening used and the specified hardness
reduction.
Fillsoft I, soft water capacity ≤ 6000/hardness red. l
Fillsoft II, soft water capacity ≤ 12000/hardness red. l
Enter the value in the controller. Consult the manufacturer
information for the values of third-party products.
This value is only displayed if "YES" has been set in the
"With softening" menu option.
Available soft water capacity.
This value is only displayed if "YES" has been set in the
"With softening" menu option.
Manufacturer specification for the replacement
interval of the softening cartridges, regardless of the
calculated soft water capacity. The system displays
the "Softening" message.
Recommended maintenance messages.
Off: Without maintenance recommendation.
001 – 060: Maintenance recommendation in months.
For the output of messages to the floating contact,  10.3
"Messages",  43.
YES: Output of all messages.
NEIN: Output of all messages identified with "xxx"
("01", for example).
Switch to the "Fault memory" sub-menu.
Press "OK" to open the menu.
Use the "▼▲" buttons to open the sub-menu.
The last 20 alarms are stored with fault type, date, time,
and fault code.
See the chapter "Messages" for more information about the
ER... messages.
Switch to the "Parameter memory" sub-menu.
Press "OK" to open the menu.
Use the "▼▲" buttons to open the sub-menu.
Commissioning
and the target
actual
-GH
l °dH
target
English — 41