Functions:
The degassing of the network water is not necessary if the circulating pumps of
the system are shut down during Summer because gas-rich water cannot reach
the device. Energy is saved.
After Summer, select the "Interval degassing" degassing programme in the
Customer menu or "Continuous degassing", if required.
For a detailed description of the selection of degassing programmes,  9.1.1
"Automatic mode",  42.
Note!
The pressurisation feature of the device must remain operative in
Summer.
Automatic mode remains active.
9.2
Restarting
CAUTION
Risk of injury due to pump start-up
Hand injuries may occur when the pump starts up if you turn the pump
motor at the impeller using a screwdriver.
Switch the pump to a zero-volts state before turning the pump at the
fan wheel with a screwdriver.
ATTENTION
Device damage due to pump start-up
Pump damage may occur when the pump starts up if you turn the pump
motor at the impeller using a screwdriver.
Switch the pump to a zero-volts state before turning the pump at the
fan wheel with a screwdriver.
After an extended standstill time (the device is de-energised or in Stop mode),
the pumps may jam. For this reason, use a screwdriver to rotate the pumps at the
fan wheel of the pump motors before restarting.
Note!
A jamming of the pumps is prevented during operation thanks to forced
starting action (after 24 hours).
10
Controller
10.1
Operator panel
1
Error LED
The Error LED illuminates in the event of a fault
2
Display
3
Auto LED
The Auto LED illuminates green in Automatic mode
The Auto LED flashes green in Manual mode
The Auto LED is not illuminated when the system is stopped
4
OK
Confirm actions
5
Stop
For commissioning and entry of new values in the controller
6
"Back" to the previous menu
7
Manual
For tests and maintenance tasks
8
9
10
11
Selecting and changing parameters
1.
Use "OK" (5) to select the parameter.
2.
Use the "▼" (7) or "▲" (9) arrow keys to change the parameter.
3.
Use "OK" (5) to confirm the parameter.
4.
Use the "▼" (7) or "▲" (9) arrow keys to switch to a different menu
option.
5.
Use "Quit" (11) to switch to a different menu level.
10.2
You can configure the controller settings regardless of the currently selected and
active operating mode.
10.2.1
This menu is protected with a password. It can be accessed only by the Reflex
Customer Service.
10.2.2
The device controller is shipped with the following default settings. Use the
Customer menu to adjust these values to local conditions. In specific cases, it is
possible to further adjust the values in the Service menu.
Customer menu
Parameter
Language
Minimum operating
pressure "P
Next maintenance
Volt-free contact
Make-up
Maximum make-up
quantity
Maximum make-up time 20 minutes
Maximum make-up
cycles
Degassing
Degassing programme
Continuous degassing
time
Softening (Only if "With
softening Yes")
Shut off make-up
Hardness reduction
Maximum make-up
quantity
Soft water capacity
Cartridge replacement
10.3
The display provides alarms in plain text and the ER codes shown in the list. Use
the arrow buttons to scroll through multiple alarms displayed at the same time.
The fault memory stores the last 20 alarms for review,  8.6 "Parametrising the
controller in the Customer menu",  40.
Alarm causes can be eliminated by the operator or a specialist workshop. If this is
not possible, contact the Reflex Customer Service.
Variomat Basic — 09.09.2022-Rev. C
Auto
For continuous operation
"Forward" to the next menu
Menu
Call up the Customer menu
Quit
Acknowledge messages
Configuring settings in the controller
Service menu
Default settings
Setting
DE
1.8 bar
"
0
12 months
All
0 Litres
3 cycles within
2 hours
Continuous
degassing
12 hours
No
8°dH
0 Litres
0 Litres
18 months
Messages
Controller
Comment
Display language.
 8.2 "Variomat switching
points",  39.
Time left to the next due
maintenance.
Only if make-up has been
selected in the customer menu
with "With water meter Yes".
Default setting
In the case of soft water residual
capacity = 0
= Target – Actual
Replace cartridge.
English — 43