4"(10,16 cm)
2 1/2"(6,35 cm)
No. of 90°
elbows
Rigid
Metallic Flexible _
Metallic Ftexibte _
0
24.4 m (80 ft.)
12.4 m (41 ft.)
10.1 m (33 ft.)
1
20.7 m (68 ft.)
11.2 m (37 ft.)
8.8 m (29 ft.)
2
17.4 m (57 ft.)
10.1 m (33 ft.)
7.6 m (25 ft.)
3
14.3m (47 ft.)
9.0 m (29 ft.)
6.5 m (21 ft.)
* Do not use non metallic flexible duct.
ELECTRIC AND GAS DRYER
Weather Hood Type
Use only for short run installation
Rigid
22.6 m (74 ft.)
18.9 m (62 ft.)
15.5 m (51 ft.)
12.5 m (41 ft.)
Exhaust
systems
longer than recommended
can extend drying times, affect machine
operation
and may collect
lint.
The exhaust
duct should
end with an exhaust
hood with a swing out damper
to prevent
back
drafts and entry of wildlife.
Never use an exhaust
hood with a magnetic
damper.
The hood should
have at least 12 inches (30.5 cm) of clearance
between
the bottom
of the
hood and the ground
or other obstruction.
The hood opening
should point down.
Never install a screen over the exhaust
outlet.
When
possible,
do not exhaust
the dryer directly
into a window
well in order to avoid lint build-
up. Do not exhaust
under a house or porch.
If exhaust
ductwork
must run through
an unheated
area, the duct should
be insulated
and slope
slightly down towards
the exhaust
hood to reduce
condensation
and lint build-up.
Inspect and clean the interior or the exhaust
system
at least once a year. Disconnect
electrical
service
prior to cleaning.
Frequently
check to be sure the exhaust
hood damper
opens and closes freely.
If newdryeris installedintoan existingexhaustsystemyou mustbe sure:
The exhaust
system
meets all local, state and national
codes.
That plastic flexible
duct is not used.
Inspect and clean all lint accumulation
from the interior of the existing
duct.
The duct is not kinked or crushed.
The exhaust
hood damper
opens and closes
freely.
The static pressure in any exhaust system must not exceed 0.83
inches of water column, or be less than 0.
This can be measured
with the dryer running with a manometer
at the point where
the exhaust duct connects
to the dryer. A no heat setting should be used.
The dryer tumbler should be empty and the lint filter clean.