Wiring the TM-RM/RM terminal submodule
• When laying the cables and connecting the submodule,
observe the regulations in EN 60079-14 plus any
applicable national regulations.
• In wiring the submodule, you must strictly separate the
intrinsically safe lines from the non-intrinsically safe. They
must be laid in separate cable ducts.
• Actuators from Zone 1, Zone 2, as well as Zones 21, 22
and the safe area may be connected to Ex-e screw
terminals of the terminal module. The terminal assignment
of the terminal module can be found in the "SIMATIC
Distributed I/O ET 200iSP" operating instructions.
• The cover of the Ex-e screw terminals must be closed
during operation.
Assembly
• Charging, connecting and disconnecting the electronic
modules is done via the Ex-d separating plug. This breaks
the circuit between the Ex-e screw terminals and the relay
contacts in the electronic module.
Commissioning
• The relevant national regulations must be observed when
commissioning the system.
• When checking the functionality of the equipment, observe
the EN 60079-17 guidelines. This standard includes the
regulations found in the international standard
IEC 60079-17.
For use in the USA and Canada
The control drawing for the ET 200iSP system is
provided with the power supply module. Alternatively, you can
find the latest edition at
https://support.industry.siemens.com,
Reference A5E00455287.