Descargar Imprimir esta página

Waeco ASC 6300 G Instrucciones De Uso página 15

Estacion de mantenimiento de aire acondicionado
Ocultar thumbs Ver también para ASC 6300 G:

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

8. Press 
STOP
.
The standby menu is displayed.
12.9 Editing default values
The A/C service unit has preset values for the most important service tasks. The default values appear
automatically when you select the respective menu.
You can alter the following default values if necessary:
Parameter
Pressure increase test time min.
Vacuum time min.
Leak test min.
PAG oil ml. (additional quantity)
UV tracer ml.
Filling Qt. g.
Display logo?
1. In the basic menu use the cursor keys   or   to select Other selections.
Short selection
Free selection
Other selections
ENTER‐OK
2. Press 
ENTER
 to confirm.
3. Use the cursor key   to select Service.
4. Press 
ENTER
 to confirm.
5. Enter the password 
7388
6. Use the keypad and the cursor keys to enter the information.
7. Press 
ENTER
 to confirm.
8. Press 
STOP
.
The standby menu is displayed.
.
Default value
1
1
4
0
0
500
Yes
    EN
15

Publicidad

loading

Este manual también es adecuado para:

Asc 6400 g9103303106