Descargar Imprimir esta página

Waeco ASC 6300 G Instrucciones De Uso página 31

Estacion de mantenimiento de aire acondicionado
Ocultar thumbs Ver también para ASC 6300 G:

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

2. Press 
ENTER
 to confirm.
3. Use the cursor keys   or   to select Reset scales.
Int. vessel filling
Flushing
Reset scales.
Service.
You are then prompted to remove the containers from the scale:
Remove the 3 Oil/UV
glasses from scales.
ENTER‐OK STOP‐EXIT
4. To check the zero point of the scales for oil and UV additive, open the cover (13) on the left side and take the
containers off the catches:
• Container for fresh oil (10)
• Container for UV additive (11)
• Drained oil receptacle (12)
5. When the scales are relieved, press 
will flash. Once you have set the zero point, the selection menu for the scales appears again.
6. Return the containers to the operating positions: Reattach the containers for oil (10) and (12) and for the UV
additive (11) to the snap locks and close the cover (13).
7. Press 
STOP
 twice to access the standby menu.
14.4 Changing the dryer filter
1. In the basic menu use the cursor keys   or   to select Free selection.
ENTER
 to confirm. The prompt to remove the containers from the scale
    EN
31

Publicidad

loading

Este manual también es adecuado para:

Asc 6400 g9103303106