Mounting Steps - Lenze L-force 9400 82 200 A Serie Instrucciones Para El Montaje

Filtro rfi
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

4
Electrical installation

Mounting steps

4.4
Mounting steps
How to connect the filter:
1. Connect filter output cables (X302/L1', L2', L3', PE') to power supply
module.
2. Remove cover .
3. Use ring cable lugs to bolt mains cables onto threaded bolts X301/L1, L2,
L3.
Observe tightening torque! ( 37)
4. Use ring cable lug to bolt mains-side PE conductor onto threaded bolt
X301/PE.
Observe tightening torque! ( 37)
PE connection must comply with EN 61800-5-1 .
5. Use cable binders to fix all mains-side cables at strain relief sheet .
6. Assemble cover .
The filter must not be commissioned without cover !
38
SSP94FF210
EDK94AZRP45 DE/EN/FR/ES/IT 2.0

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

L-force e94azrp0824L-force e94azrp2004

Tabla de contenido