SW1
Main/sub selection switch
OFF: Central controller operates as main controller.
ON: Central controller operates as sub-controller.
ALL/ZONE mode selection switch
ALL mode:
All indoor units can be controlled by central controller.
ZONE 1, 2, 3, 4 mode:
Indoor units in one of zone 1, 2, 3, or 4 can be controlled by
central controller. All indoor units cannot be set.
ALL mode
ZONE 1 mode
ZONE 2 mode
ZONE 3 mode
ZONE 4 mode
Central control/Remote control mode selection switch
OFF: Central control mode.
Individual setting by remote controller can be inhibited by
central controller.
ON: Remote control mode.
Setting by central controller is inhibited by other central
control equipments.
Central control Main/Sub selection switch
(OFF: Main, ON: Sub)
1
When AMY adaptor etc. is used with central controller,
set the switch to ON position.
2
When only one central controller is used, set the switch to
OFF position.
3
Except
1
only one central controller to OFF position and others to
ON position.
ALL mode central controller to be OFF position.
(recommended)
(Central control) button operation switch
OFF:
(Central control) button operation is permitted.
ON :
button operation is inhibited.
*All switches are OFF position at shipment.
OI-607-11EG
2
3
OFF
OFF
OFF
OFF
ON
OFF
OFF
ON
ON
ON
, when multiple central controllers are used, set
ON
OFF
4
5
OFF
ON
OFF
ON
ON
ON
SW1
1
2 3 4
5 6 7 8
Fig. 10