MOUNT THE REFLECTOR USING THE DRILL TEMPLATE
Refer to Appendix II. in Installation guide for drill template instructions.
MOUNTING THE DETECTOR
Remove detachable front rim cover. To detach the Imager part from the backbox,
loosen the 3 holding screws.
To provide cable access to the Termination Card of the Imager remove the cut-outs
from the back, bottom or top of the main assembly by using a sharp blade to cut
around the circular discs.
Secure the back box directly onto the mounting surface using any suitable number of
the 5 pilot holes in the backbox.
Use appropriate fasteners to secure the back box component to the mounting surface.
FIGURE 4.MOUNTING THE DETECTOR
Holes for the fixing
of the detector
Mounting holes
WIRE THE TERMINATION CARD ON THE IMAGER
• Wire the initiating device circuit on the Imager Termination Card using the
addressable loop. (See Figure 5.)
• Wire external power to the unit via the POWER terminals.
• Wire the Remote Indicator and/or remote test or reset units if required (See
Figure 6.).
• Securely connect the wires to the plug-in terminals and engage in the recep-
tacles at the back of the Imager.
• Switch on the heater if the installation requires so.
• Set the detector address using the rotary switches
• Re-attach the Imager to the back box
• Remove the protective film from the lens surface of the imager.
• Connect power to the Imager.
FIGURE 5. WIRING THE TERMINATION CARD
FIGURE 6. WIRING THE TERMINATION CARD
Cable knock-outs
top
No heater
Isolator
Large knock-out
for 4" J-Box
FIGURE 7. OSI-RI TERMINALS
Cable knock-outs
bottom
C2055-00
FIGURE 8. REMOTE LED CONNECTIONS
Not Used
T3
Not Used
Heater Power In -
Heater Power In +
AUX (-)
Remote Test/Reset Input
Remote Trouble Output
T2
USB
Remote Alarm Output
Connector
SLC - OUT
SLC - IN
T1
SLC + OUT
SLC + IN
C2056-00
2
Jumper
Heater on/off switch
heater
shunts
+
-
Heater
From panel
No Isolator
or previous
device
OSI-RIE-xx Terminals
Remote Alarm Output
T2-1
Remote Trouble Output
T2-2
Remote Test/Reset Input
T2-3
AUX -
T2-4
10k ohm
External
Resistor
Wiring: Single 2 pair cable , 0.8mm
T2-1
Alarm
Signal
Circuit
T2-2
Trouble
Signal
Circuit
T2-4
Remote LED connections
Rotary switches
for setting
the address
Heater
Power
In -
Heater
Power
In +
-
+
Communication Line
To next
32 VDC max.
device
Twisted pair is
recommended
C2057-00
RTS151/Key
Terminals
T1
T3
External
Jumper
T4
T5
T2
2
, unshielded.
C2058-00
Red
Yellow
C2059-00
I56-6965-001
01/16/2023