OPERATION MODES AND TROUBLESHOOTING GUIDE OSI-RIE-xx (SEE FIGURES 10. AND 11.):
Modes
Red and
Remote Alarm
output
(LED 1)
Power on
Off
Alignment
Off
Initializing/ Com-
Off
missioning
Normal
Off
Alarm
On
Trouble-Drift
Off
Compensation
Trouble-Beam
Off
Blockage
Trouble-Imager
Off
saturation
Test activated-
On
Pass Result
0333
20
Pittway Tecnologica S.r.l.,
Via Caboto 19/3,
34147 TRIESTE, Italy
DOP-LPB023
EN 54-12:2015
Line Detector using an Optical Beam, Fire Safety
EN 54-17:2005
Short Circuit Isolator
Please refer to the insert for the Limitations of Fire Alarm Systems.
For warranty terms, please refer to the Product Guide found at www.systemsensoreurope.com/products/category/beam-smoke-detectors/.
System Sensor® is registered trademarks of Honeywell International Inc.
Yellow and Remote
Green
Trouble Output
(LED 3)
(LED 2)
Blink
Off
Blink
Off
Blink
Off
Off
Blink
Off
Off
3 Quick Blinks
Blink
4 Quick Blinks
Blink
5 Quick Blinks
Blink
Blinks the set sensi-
Off
tivity by number of
blinks (1-4). Repeats
every 3 seconds till
reset.
Initiating means
Apply Power from dis-
• All wiring correctly done.
charged state
• Address switches set.
Lever in 3:00 position and
• Ready to perform alignment.
commissioning is active
• Follow guidance from the 4 arrows to correctly align.
Lock lever in 6:00 position
• Commissioning and setting sensitivity.
to start commissioning
• Do not interrupt beam.
Successful completion of
• Initializing finished.
initialization or detector
• Detector operates normal in quiescent condition.
reset
• Detector successfully reset.
Smoke, Test Filter or RTS-
• Blinks till reset from FACP.
151KEY Test Station
Long Term Drift Reference
• Reduced IR Signal
Out of 20% Range
• Clean detector and reflector.
Beam blockage or detector
• Remove blockage or re-align detector
out of alignment
• Faulty unit.
Imager saturated
• Sunlight or very strong light into detector or reflector.
• Re-position detector or reflector.
• Remove light source.
FACP or RTS151KEY
• Remains in alarm until reset by FACP.
• Number of lit arrows indicates sensitivity level that was
selected automatically.
DISCLAIMER