EN: Installation Sheet
Product description
The 6540, 6550 and 6540PI are designed to detect movement
of an intruder and activate an alarm control panel. The product
is intended to be connected to a listed burglar compatible
control unit or a power supply that has a voltage output range
of between 9 to 15 VDC and provides a minimum of 4 hours of
standby power.
Installation guidelines
The technology used in these detectors resists false alarm
hazards. However, avoid potential causes of instability such as
(see Fig. 1):
Direct sunlight on the detector.
Heat sources within the detector field of view.
Strong draughts onto the detector.
Large animals within the detector field of view. (except for
pet immune version)
Obscuring the detector field of view with large objects,
such as furniture.
Not suitable for outdoor use.
Installing the detector
1.
Unwind the screw at the base of the detector until loose;
the screw will be retained in the product (see Fig. 2, step
1)
2.
Lift detector lid out from the base and off the lugs at the
top (see Fig. 2, step 2)
3.
Fix the base to the wall between 1.5 m and 3.1 m (4.1 and
10 ft) from the floor. For flat mounting use a minimum of 2
screws (DIN 7998) in positions A (see Fig. 3). For corner
mounting use screws in positions B or C (see Fig. 3)
4.
Set the mounting height by adjusting the position of the
PCB (see Fig. 4)
5.
Wire the detector (see Fig. 4 and 10). For the dual loop
connection wiring diagram, see Fig. 11.
6.
Select the desired jumper settings (see Fig. 4). See the
'Jumper settings' section for more information.
7.
Add masking labels if required (see Fig. 9 for an example)
For ceiling mount applications that require a 90° coverage
8.
use the optional swivel-mount bracket (Part Number:
6545-BP)
9.
Replace lid and tighten the screw in a base.
For bracket installation see Fig. 13.
Jumper settings
(See Fig. 4 for jumper locations in the detector.)
Alarm Jumper
OFF: Alarm in open circuit
4 / 25
ON: End of line resistor value 3k3
Tamper Jumper
OFF: Tamper in open circuit
ON: End of line resistor value 3k3
Input Invert Jumper
LEFT: Not inverted
RIGHT: Input inverted
Walk Test Jumper
LEFT: Walk test enabled
RIGHT: Walk test under input control
Pulse Count Jumper
See Fig. 8.
LEFT: Pulse Count 1 (high sensitivity required for EN50131-2-
2)
RIGHT: Pulse Count 2 (normal sensitivity)
Wiring
For the ex-factory settings, see Figure 10.
For the dual loop connection wiring diagram, see Figure 11.
Walk test (WT) voltage - Open Collector, 0 V active.
Accessory lenses
For cover pattern for accessory lenses (only for use on the
6540), see Figure 12.
To change the lens see Fig. 14.
LED Indication
PIR Function
Red LED
Start Up
Normal
Blinking (1Hz)
PIR Intruder
Continuously
Alarm
On
Specifications
Type
6540
Detector
PIR
Signal processing
DSP
Range
12 m
Optical
Fresnel Lens Holographic-
Pet immunity
-
Alarm Relay
To Reset
Closed
Automatically
after 60 seconds
Open (Alarm)
Automatically
after a minimum
of 2 seconds
6540PI
6550
PIR
PIR
DSP
DSP
12 m
15 m
Fresnel Lens
Fresnel Lens
-
Up to
<20kg/44lbs
P/N INS518 • REV B • ISS 12MAR19