Water calculation mode:
Selection of the water set point
for Circuit 1 or Circuit 2 (Space
Heating or Space Cooling).
• Disabled
• Points
• Gradient (only in heating mode)
• Fix
See detailed explanation below.
Eco Offset Water setting:
Configure the offset water
temperature for the ECO mode
for Space Heating or Space
Cooling.
By using this function, current
water temperature setting
is reduced by the indicated
parameter.
• Range: -10 ~ 10
PMEN0602 rev.0 - 05/2023
Working Limits:
Limit for the temperature set-point
to prevent high or low temperatures
at Space Heating or Space Cooling:
• Maximum supply temperature
• Minimum supply temperature
Mixing valve:
To control the second water
temperature (only for circuit 2).
Values are adjusted for the use
with the 2nd zone mixing kit
accessory ATW-2KT-05. It is highly
recommended not to change these
values.
In case of using a mixing kit different
from the ATW-2KT-05 configure the
following parameters:
• Proportional band: 0 ~20 K (6.0 K
by default).
• Integral reset factor: 0.0 ~20 % (2.5
% by default).
• Running time factor: 10 ~250 sec
(140 sec by default).
• Over temperature offset
protection: OFF, 3 ~10 ºC (5 ºC by
default).