Example: (default setting)
In the last 480 minutes (time spending)
the make-up water quantity per cycle
must not exceed 50 litres. Moreover, it is
not permissible to supply this quantity
during this time more than three times, and
the pauses between the cycles must be 5
minutes at a minimum.
Item
Max. quantity/filling
- Maximum allowable quantity per cycle (also per cycle) with integrated and configured
pulse water meter. See section Monitoring: make-up quantity
Max. time/filling
- Maximum allowable make-up time per cycle (also per cycle).
See section Monitoring: monitoring of run time
Min. interval between 2 cycles
- Minimum interval between two cycles (pause)
Max. cycles/time spend
- Maximum number of cycles per time window
Time spending
- Size of time window
Note that the values in the filling quantity
menu are interdependent. Therefore, it may
be necessary to first parameterise another
value before the actual value becomes
accessible within the intended limits.
Similarly, setting ranges may be limited
by the dependencies. It is advisable, for
instance, to first parameterise a sufficiently
sized time window before defining the
pauses and the number and length of cycles.
Item
Time and date
- Summer time on: starting month
(summer time ON is 00 for regions without change between times)
- Summer time off: ending month
(summer time OFF=00 for regions without change between times)
- Maintenance gap: maintenance interval 0 .. 800 days
- Pressure sensor min.value
- Pressure sensor max.value
Installation and operating instructions Tagus Vac 7-30
Factory setting
150 hours
20 minutes
5.0 minutes
3
480 minutes
Factory setting
Operator task
03
10
365 days
0.0 bar
10.0 bar
English