6. OPERATION.
6.1. START-UP.
6.1.1. Checks before start-up.
Make sure that all of the connections have been made
•
correctly, following the instructions on the labelling of the
device and in Chapter .
Check that the switch on the battery module or modules is 'Off'.
•
Make sure that all loads are 'Off'.
•
Shut down the connected loads before starting the
UPS and start the loads, one by one, only when the
UPS is running. Before shutting down the UPS, check that all of
the loads are 'Off'.
It is very important to proceed in the established order.
•
For views of the UPS, see .. .
•
6.2. UPS START-UP AND SHUTDOWN.
6.2.1. UPS start-up with mains voltage.
Check that the power connection is correct.
•
Turn the battery module switch to 'On' (models B0 and B1).
•
Supply voltage to the device (turn the input protection on the
•
distribution board to 'On'). If the board has an output switch,
turn it to 'On'.
All of the models in this series have an input polarity
•
detector (phase-neutral), which activates a modulated
audible alarm every 2 seconds and displays the message on
SF
the '
' display in the event of a fault.
When the circumstance arises, disconnect the plug from the
mains socket and rotate it 180º.
If the same alarm condition is maintained, it will be a two-phase
power line signal or installation without neutral referenced to
earth. Contact our T.S.S. or the distributor before connecting
loads to the output.
The fan or fans, depending on the model, will start to function.
•
Then the main start screen will be displayed after a test of the
device.
Press the ON/MUTE button for more than 2 seconds, the
•
audible alarm will sound for 1 second, the UPS will start up and
an automatic battery test lasting 10 seconds will begin.
After a few seconds, the UPS will be in 'Normal mode'. If the
•
mains voltage is incorrect, the UPS will switch to 'Battery
mode', without interrupting the power supply at the output
terminals.
Start the load or loads, making sure that the rated power of the
•
device is not exceeded.
54
6.2.2. UPS start-up without mains voltage.
If it has a distribution board, turn the input and output
•
protections to 'On'.
Turn the battery switch to 'On' (B0 and B1).
•
Press the ON/MUTE button for more than 2 seconds, the
•
audible alarm will sound for 1 second and the UPS will start up.
The fan or fans, depending on the model, will start to function.
Then the main start screen will be displayed after a test of the
device.
After a few seconds, the UPS will be in 'Battery mode',
•
meaning that its charge level and therefore available residual
backup, as well as the risks associated with operating in this
mode, must be taken into consideration.
If the mains voltage returns, the UPS will transfer to 'Normal
mode' without interrupting the power supply at the output
terminals.
Start the load or loads, making sure that the rated power of the
•
device is not exceeded.
6.2.3. UPS shutdown with mains voltage.
Shutdown the load or loads.
•
Press the OFF/ENTER button for more than 2 seconds to shut
•
down the inverter. The audible alarm will sound for 1 second.
The device is in Standby (no output voltage) and charging
batteries.
6.2.4. UPS shutdown without mains voltage.
Shutdown the load or loads.
•
Press the OFF/ENTER button for more than 2 seconds to shut
•
down the inverter. The audible alarm will sound for 1 second.
The device will leave the output terminals without voltage.
A few seconds later, the LCD screen turns off and the entire
device will be out of service.
To leave the assembly completely isolated, turn the input and
•
output switches of the board to 'Off'.
SALICRU