Descargar Imprimir esta página

Salicru SPS.ADVANCE RT2 Manual De Usuario página 56

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

Code
On display
bL
BL
OL
OL
NC
NC
OC
OC
SF
SF
TP
TP
CH
CH
bF
BF
bR
BR
EE
EE
Tab. 7. Abbreviations shown on the LCD display.
7.2. COMPOSITION OF THE CONTROL
PANEL WITH LCD DISPLAY.
The control panel consists of:
Three buttons with the functions described in .
ˆ
An LCD display with backlighting.
ˆ
ON/MUTE
Fig. 16. View of the control panel.
56
Meaning
Low battery.
Overload.
Battery not connected
Battery overcharge
Connection error. Rotate the connection of the
input, phase and neutral cables.
Overtemperature.
Charger
Battery failure, low voltage.
Replace batteries.
Internal EEPROM error.
SELECT
OFF/ENTER
Button
- Starting up the UPS.
Press the button for at least 2 seconds.
- Muting the alarm.
Press the button for at least 3 seconds to mute or unmute
the audible alarm.
It is only possible to mute the battery discharge alarm,
which necessarily means that the device is running and
operating in battery mode. Any other warning or error alarm
ON/MUTE
cannot be muted.
- Button to navigate upwards.
When this button is pressed in UPS settings mode, it will
move upwards through the menu structure in relation to the
point where it is located, accessing the previous variable
with each press.
- Activating the battery test.
Press this button for 3 seconds while in normal or frequency
converter (CF) mode. At the end of the test, it returns to the
respective mode.
- Changing the LCD screen display.
Press this button to change the message on the display
to read input voltage, input frequency, battery voltage,
battery level, ambient temperature, output voltage, output
frequency, load consumption and percentage of load
consumption.
SELECT
- Settings or configuration mode.
Press this button for at least 3 seconds to access this mode
when the inverter of the UPS is shut down.
- Button to navigate downwards.
When this button is pressed in UPS settings mode, it will
move downwards through the menu structure in relation
to the point where it is located, accessing the following
variable with each press.
- UPS shutdown.
Press this button for at least 2 seconds.
OFF/ENTER
- Confirmation of selection.
Press this button to confirm selection in the device's settings
mode.
Tab. 8. Functionality of the control panel buttons.
7.3. AUDIBLE ALARMS.
Description
Alarm modulation or tone
State of the UPS
Battery mode
Beep every 10 s
Warning
Polarity error
Beep every 2 s
Low battery
Beep every 2 s
Overload
Beep every 1 s
Faults
All
Continuous.
Tab. 9. Audible alarms.
Description
Possibility
of muting
Yes
Yes
No
SALICRU

Publicidad

loading